11-6. HOW TO CHECK THE PARTS

PU(H)-P71VHA
.UK
(1)
PU(H)-P125YHA
.UK
(1)
PU(H)-P71VHA#2.UK
PU(H)-P125YHA#2.UK PU(H)-P140YHA#2.UK
PU(H)-P71VHAR3.UK
PU(H)-P125YHAR3.UK PU(H)-P140YHAR3.UK
PU(H)-P125YHAR4.UK PU(H)-P140YHAR4.UK
Parts name
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge/Compressor surface>
Thermistor (TH6)
<Outdoor 2-phase pipe>
FAN MOTOR(MF)
P71, P125, P140
P100
Black
Red
White
FUSE
OPEN:141
Protector
OPEN:135 5
Solenoid valve coil (21S4)
<Four-way valve>
Motor for compressor (MC)
U
V
W
Linear expansion valve (LEV)
Gray
M
1
2
Orange
3
Red
4
Yellow
5
Black
6
Solenoid valve coil (SV)
<Bypass valve>
For P125, P140
CRNKCASE HEATER (CH)
OC379F
PU(H)-P100VHA
.UK
(1)
PU(H)-P140YHA
.UK
(1)
PU(H)-P100VHA#2.UK
PU(H)-P100VHAR3.UK
Disconnect the connector then measure the resistance with a tester.
(Surrounding temperature 10 ~30 )
TH4
TH3
TH6
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20 )
Black
Motor lead wire
Orange
White — Black
Red
White
White — Red
Protector
OPEN :140 5
CLOSE :90 15
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20 )
P71,P100
1500 ± 150
Measure the resistance between the terminals with a tester.
(Winding temperature 20 )
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20 )
Gray - Black
Measure the resistance between the terminals with a tester.
(Surrounding temperature 20 )
Measure the resistance between the terminals with a tester.
PU(H)-P71YHA
.UK
(1)
PU(H)-P71YHA#2.UK
PU(H)-P71YHAR3.UK
Check points
Normal
160k ~410k
4.3k ~9.6k
Normal
P71, P125, P140
P100
82.5 ±10%
44.5 ±7%
102.0 ±10%
43.7 ±7%
Normal
P125,P140
1435 ± 150
Normal
Refer to 6-2.
Normal
Gray - Red Gray - Yellow Gray - Orange
46 ± 3
Normal
1450 ± 150
Normal
P71,P100,P125,P140
2304
± 7%
50
PU(H)-P100YHA
.UK
(1)
PU(H)-P100YHA#2.UK
PU(H)-P100YHAR3.UK
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Open or short

Hide quick links: