M-Net Wiring Method - Mitsubishi Electric Mr.SLIM PU-P71VHA Service Manual

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr.SLIM PU-P71VHA:
Table of Contents

Advertisement

9-4. M-NET WIRING METHOD

(Points to note)
(1) Outside the unit, transmission wires should stay away from electric wires in order to prevent electromagnetic noise from
making an influence on the signal communication. Place them at intervals of more than 5cm. Do not put them in the same
conduit tube.
(2) Terminal block (TB7) for transmission wires should never be connected to 220~240V power supply. If it is connected,
electronic parts on M-NET P.C. board may be burn out.
(3) Use 2-core x 1.25mm
2
received normally if different types of transmission wires are put together in the same multi-conductor cable. Never do this
because this may cause a malfunction.
Group
remote
controller
It would be ok if M-NET wire (non-polar, 2-cores) is arranged in addition to the wiring for A-control.
(4) Earth only one of any appliances through M-NET transmission wire (shield wire). Communication error may occur due to
the influence of electromagnetic noise.
"Ed" error will appear on the LED display of outdoor unit.
"0403" error will appear on the central-control remote controller.
×
Central
remote
controller
M-NET transmission wire
Central
remote
controller
M-NET transmission wire
Central
remote
controller
M-NET transmission wire
If there are more than two earthing spots on the shield wire, noise may enter into the shield wire because the earth wire
and shield wire form one circuit and the electric potential difference occurs due to the impedance difference among earth-
ing spots. In case of single spot earthing, noise does not enter into the shield wire because the earth wire and shield wire
do not form one circuit.
To avoid communication errors caused by noise, make sure to observe the single spot earthing method described in the
installation manual.
OC379F
shield wire (CVVS, CPEVS) for the transmission wire. Transmission signals may not be sent or
Power
supply
unit for
transmission
wire
A-control
remote
controller
Bad example (Multi spot grounding of shield wire)
Power
M-NET type
supply
outdoor unit
appliance
Good example 1 (Single spot grounding of shield wire)
Power
M-NET type
supply
outdoor unit
appliance
Good example 2 (Single spot grounding of shield wire)
Power
M-NET type
supply
outdoor unit
appliance
Refrigerant
Refrigerant
address 00
address 00
M-NET
M-NET
address 01
address 02
A-control
remote
controller
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit
26
Refrigerant
address 00
M-NET
address 03
A-control
remote
controller
M-NET type
outdoor unit
M-NET type
outdoor unit
M-NET type
outdoor unit