Wiring Schematics cont.
Aurora Base with PSC cont.
With optional ' EA' Series
Auxiliary Electric Heat
Typical schematic shown
Green
Brown
Orange
NOTE 4
Condensate
Aurora LED Flash Codes
Slow Flash
1 second on and 1 second off
Fast Flash
100 milliseconds on and 100 milliseconds off
Flash Code
100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Random Start Delay (Alternating Colors)
Configuration LED (LED2, Yellow)
Status LED (LED1, Green)
Fast Flash
No Software Overide
Fast Flash
Configuration LED (LED2, Yellow)
DIP Switch Overide
Fault LED (LED3, Red)
Fast Flash
Fault LED (LED1, Red)
Status LED (LED3, Green)
Normal Mode
OFF
Normal Mode
Input Fault Lockout
Flash Code 1
Control is Non-Functional
High Pressure Lockout
Flash Code 2
Test Mode
Low Pressure Lockout
Flash Code 3
Lockout Active
Future Use
Flash Code 4
Dehumidification Mode
Freeze Detection – FP1
Flash Code 5
Future Use
Reserved
Flash Code 6
Future Use
Condensate Overflow Lockout
Flash Code 7
Load Shed
Over/Under Voltage Shutdown
Flash Code 8
ESD
Future Use
Flash Code 9
Future Use
Future Use
Flash Code 10
FP1 and FP2 Sensor Error
Flash Code 11
208-230/60/1
208-230/60/1
Circuit 2
Circuit 1
NOTE 3
G
L2
L1
L2
L1
G
P9
1
2
3
Brown
5
4
Orange
PB2
Pink
Black
ER1
Yellow
Gray
G
NO
ER2
G
NO
ER3
NO
G
ER4
G
NO
EA Series PCB
P2
P1
C
1
2
3
4
3
C
1
2
4
EA Staging
NOTE 5
C EH1 C
CO
EH2
P3
P3 on ABC Board
Aurora Timing Events
Event
Random Start Delay
Compressor On Delay
Compressor Minimum On Time
OFF
Compressor Short Cycle Delay
Slow Flash
Blower Off Delay
Fault Recognition Delay – High Pressure
Start-Up Bypass – Low Pressure
ON
Fault Recognition Delay – Low Pressure
OFF
Start-Up Bypass – Low Water Coil Limit
Slow Flash
Fault Recognition Delay – Low Water Coil Limit
Fast Flash
Fault Recognition Delay – Condensate Overflow
Flash Code 2
Thermostat Call Recognition Time
Flash Code 3
Comfort Alert Recognition Time
Flash Code 4
Auxiliary Heat Staging Delay
Flash Code 5
Emergency Heat Staging Delay
Flash Code 6
Water Valve Slow Open Delay
Flash Code 7
ABC SW2 Accessory Relay
DESCRIPTION
Cycle with Blower
Cycle with Compressor
Water Valve Slow Opening
Cycle with Comm. T-stat Hum Cmd
AFFINITY SINGLE & DUAL CAPACITY SERIES INSTALLATION MANUAL
Auxiliary Electric Heat Power
Pink
Yellow
Black
Gray
Gray
HE1
TS1
Gray
Black
Black
HE2
TS2
Yellow
Yellow
Pink
HE3
TS3
Pink
HE4
TS4
CSA installed units only
Local codes may require a single
source of power supply
Single Disconnect Power
208-230/60/1
Breaker box
L1
L2
furnished by
installer
Circuit Breakers
L1
L2
L1
L2
Aux Elect Power
Unit Power
208-230/60/1
208-230/60/1
Normal Mode
Test Mode
UNIT
5 to 80 seconds
1 second
12
5 seconds
< 1 second
2 minutes
5 seconds
18
4 minutes
15 seconds
22
30 seconds
2 seconds
30
Less than 1 second
Less than 1 second
36
2 minutes
30 seconds
30 seconds
30 seconds
42
2 minutes
30 seconds
48
30 seconds
30 seconds
60
30 seconds
30 seconds
2 seconds
2 seconds
70
90 seconds
90 seconds
UNIT
5 minutes
20 seconds
22
2 minutes
7.5 seconds
90 seconds
90 seconds
30
36
42
SW2-4
SW2-5
48
ON
ON
OFF
OFF
ON
OFF
OFF
ON
45
Legend
Factory Low voltage wiring
Factory Line voltage wiring
Field low voltage wiring
Field line voltage wiring
Optional block
DC Voltage PCB traces
Junction
Quick connect terminal
Wire nut
Field wire lug
L1
Ground
Relay Contacts-
2
N.O., N.C.
P
Fuse
Breaker
CC -
Compressor Contactor
CO -
Condensate overflow sensor
K5 -
DHW pump relay
Loop pump relay
K6 -
PSC Fan Speed Relay
CR3 -
PSC Fan Power Relay
CR4 -
CS -
Compressor Solenoid
F1 and F2 -
Fuses
HE -
Heater element
HP -
High pressure switch
ER1 to ER4 -
Aux heat stage relays
LP -
Low pressure switch
Notes
1 - Switch blue and red wires for 208V operation.
2 - The blk/wh and gray/wh wires are removed when Aux Heat is installed
3 - Use manufacturer's part number 19P592-01 (jumper bar assembly) when single source power is
required.
4 - When connected the Auxiliary Heat powers blower and controls. Wires are secured at blower.
5 - For additional Auxiliary Heat staging place jumpers as shown.
6 - Refer to FAN SPEED table for factory settings.
7 - Wires provided for Auxiliary Heat low voltage control. Wires are secured at blower.
FACTORY SET FAN SPEED
STANDARD PSC
H
M
M
M
M
M
M
M
H
HIGH STATIC PSC
M
M
M
M
M
97P840-05
6/ 22/ 12
Thermistor
T
Light emitting diode - Green
G
Relay coil
Capacitor w/ bleed resistor
Switch - Condensate overflow
Switch - High pressure
Switch - Low pressure
3
1
Polarized connector
Current Transducer (CT)
PB1, PB2 -
Power blocks
PS -
Power strip
RV -
Reversing Valve coil
SW1 -
DIP package 5 position AXB
SW1 -
TEST MODE ABC Board
SW2 -
DIP package 8 position ABC Board
TS -
Thermal limit switch
HWL -
Hot water limit sensor
SC -
Start Contactor
SR -
Start Relay
WCL -
Water Coil Limit Sensor