Potterton Eurocondense three Programming Manual page 15

125 to 300kw floor standing condensing gas boilers
Table of Contents

Advertisement

Function
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
DHW
DHW-Operating mode
Off | On | Eco
Nominal setpoint
Reduced setpoint
Release
24h/day | Time programs HCs | Time program 4/DHW | Low tariff |
Time program 4/DHW or LT
Charging priority
Absolute | Shifting | None | MC shifting, PC absolute
Legionella function
Off | Periodically | Fixed weekday
Legionella funct periodically
Legionella funct weekday
Monday | Tuesday | Wednesday | Thursday | Friday | Saturday | Sun-
day
Legionella funct time
Legionella funct setpoint
Legionella funct duration
Legionella function circ pump
Off | On
Circulating pump release
Time programme 3 / HCP | DHW release | Time programme 4/DHW |
Time program 5
Circulating pump cycling
Off | On
Circulation setpoint
Optg mode changeover
None | Off | On
Consumer circuit 1
Flow temp setp cons request
DHW charging priority
- No | Yes
Excess heat draw
- Off | On
With buffer storage tank
- No | Yes
With prim contr/system pump
- No | Yes
Consumer circuit 2
Flow temp setp cons request
DHW charging priority
No | Yes
Excess heat draw
Off | On
358 488 09.10
Gas-fired fuel value boiler EuroCondense three 125-300 kW
Programming
Prog.
Standard value
1)
Level
no.
1500
E
Protection
1600
E
ON
1610
E
55°C
1612
F
40°C
1620
E
Time programmes HCs
1630
F
MC shifting, PC absolute
1640
F
Fixed weekday
1641
F
3
1642
F
Monday
1644
F
- - -
1645
F
65°C
1646
F
30 min
1647
F
ON
1660
C
DHW release
1661
C
ON
1663
F
45°C
1680
F
Off
1859
C
70°C
1874
E
Yes
1875
E
ON
1878
E
Yes
1880
E
Yes
1909
C
70°C
1924
E
Yes
1925
E
ON
15