The following table summarizes the peak (at startup) power consumed by the system and the heat it generates
under the maximum processing load produced by a Visual Effects, Finishing, or Colour Grading application.
For more detailed specifications, including noise output, see the documentation provided by the manufacturer.
Component
Workstation (with cards)
Lucid ADA 88192
®
Stone
Direct XR storage
chassis
Stone Direct XE expansion
chassis
Stone Direct XR + Stone
Direct XE
®
Autodesk
Control Surface
(Lustre only)
You must be able to meet the startup power requirement and have a climate control system with the capacity
to maintain the temperature of these components under the maximum processing load. The following table
shows standard conversion benchmarks and an example of how they can be used to determine climate
control requirements.
Unit Conversion
1 Watt = 3.413 BTU
12000 BTU = 1 Ton of air conditioning

Rack Mount Requirements

If you plan to rack-mount your system, allow sufficient space for each component, as indicated in the
following table.
Component
Workstation
AJA OEM-2K breakout box
Stone Direct XR storage chassis
Stone Direct XE expansion chassis (optional)

Avoiding Damage from Static Electricity

Take precautions to prevent damage to sensitive components from static discharge:
Make sure power is turned off on the component you are working on. It is a good idea to unplug
components until all other connections are configured.
10 | Chapter 2 Getting Started
Quantity
Startup Amps
(120V / 240V)
1
4.0 / 2.0
1
0.5 / 0.25
1
3.8 / 1.9
1
3.75 / 1.88
1
6.41 / 3.2
1
1 / 0.5
Example
456 Watts = 1556.33 BTU
1556.33 BTU = 0.13 Tons of air conditioning
Quantity
1
1
1
1
Cont. Amps (120V
Watts
/ 240V)
3.8 / 1.9
456
0.5 / 0.25
60
2.78 / 1.39
334
2.3 / 1.15
276
5.2 / 2.6
624
1 / 0.5
120
Form Factor
Required Rack Space
5U
5U
1U
1U
2U
2U
2U
2U
Heat (BTUs)
1556
205
1140
942
2130
410