4
Interfaces
Serial Interface (HOST-I/F)
This interface is used to connect the GP to the host (PLC), via an RS-232C or RS-
422 cable.
Pin Arrangement
1
13
Recommended Connector: Dsub 25 pin plug XM2A-2501 <made by OMRON Corp.>
Recommended Cover
Recommended Cable
• This GP unit's serial port is not isolated. When the host (PLC) unit is
also not isolated, and to reduce the risk of damaging the RS-422 circuit,
be sure to connect the #7 SG (Signal Ground) terminal.
• Pin #14 (VCC) DC 5V Output is not protected. To prevent damage or unit
malfunction, use only the designated level of current.
• Inside the GP unit, the SG (Signal Ground) and FG (Frame Ground) ter-
minals are connected to each other.
• When connecting an external device to the GP with the SG terminal,
ensure that no short-circuit loop is created when you setup the system.
Signal
Pin #
Name
1
2
3
4
5
6
7
8
9
TRMX
14
10
RDA
11
SDA
12
13
14
VCC
15
SDB
16
RDB
25
17
18
CSB
19
ERB
20
21
CSA
22
ERA
23
24
25
: Dsub 25 pin Cover XM2S-2511 <made by OMRON Corp.>
Jack Screw XM2Z-0071 <made by OMRON Corp.>
: CO-MA-VV-SB5P x 28AWG
<made by HITACHI Cable Ltd.>
FG
Frame Ground
SD
Send Data (RS-232C)
RD
Receive Data (RS-232C)
RS
Request to Send (RS-232C)
CS
Clear to Send (RS-232C)
DR
Data Set Ready (RS-232C)
SG
Signal Ground
CD
Carrier Detect (RS-232C)
Termination (RS-422)
Receive Data A (RS-422)
Send Data A (RS-422)
NC
No Connection(Reserved)
NC
No Connection(Reserved)
5V±5% Output 0.25A
Send Data B (RS-422)
Receive Data B (RS-422)
RI
Ring Indicate (RS-232C)
Clear to Send B (RS-422)
Enable Receive B (RS-422)
ER
Enable Receive (RS-232C)
Clear to Send A (RS-422)
Enable Receive A (RS-422)
NC
No Connection(Reserved)
NC
No Connection(Reserved)
NC
No Connection(Reserved)
Meaning

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gp2600-tc41-24v

Table of Contents