Output Over Current Detection - Daikin SiEN04-306D Service Manual

Inverter pair wall mounted type b-series
Table of Contents

Advertisement

Troubleshooting

4.19 Output Over Current Detection

L5
remote control
Display
Method of
An output over-current is detected by checking the current that flows in the inverter DC section.
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed
Causes
134
A position signal error occurs while the compressor is running.
A speed error occurs while the compressor is running.
An output over-current input is fed from the output over-current detection circuit to the
microcomputer.
The system will be shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Over-current due to defective power transistor
Over-current due to wrong internal wiring
Over-current due to abnormal supply voltage
Over-current due to defective PCB
Error detection due to defective PCB
Over-current due to closed stop valve
Over-current due to compressor failure
Over-current due to poor installation condition
SiEN04-306D
Service Diagnosis