Operation
1. Water Flow Begins
Water Flow Sensor sends pulses to the PCB.
PCB senses flow greater than 0.5 GPM (0 GPM for "A" Model) (approximate).
Firing Sequence begins.
2. Firing Sequence
PCB monitors Inlet / Outlet water temperature, temperature set point,
and water flow rate.
Fan Motor energized. Purges combustion chamber.
Spark igniter begins sparking
Main Gas control valve opens to minimum fire rate.
Flame rod proves ignition.
Spark igniter stops sparking.
3. Normal Operation
PCB monitors flame rod, fan motor frequency, outlet water temperature,
PCB temperature set point and water flow rate.
Main Gas control valve modulates gas input to required firing rate.
Combustion fan speed is adjusted for the required firing rate.
Water adjustment valve is adjusted as needed.
4. Shut-down Sequence
PCB senses flow rate less than 0.5 GPM (0 GPM for "A" Model) (approximate).
Main Gas Control valve closes.
Water adjustment valve resets to standby position.
Combustion fan runs for a short period of time at low speed.
5. Standby Mode
PCB monitors water temperature and remote controls.
Freeze protection is activated as needed.