Carrier 48AJ Operating And Service Manual page 88

Single package large rooftop units with scroll compressors and comfort link version 4.x controls
Table of Contents

Advertisement

ALARM
OR
ALERT
NUMBER
T300
Space Temperature Below Limit
T301
Space Temperature Above Limit
T302
Supply Temperature Below Limit
T303
Supply Temperature Above Limit
T304
Return Temperature Below Limit
T305
Return Temperature Above Limit
T308
Return Air Relative Humidity Below Limit
T309
Return Air Relative Humidity Above Limit
T310
Supply Duct Static Pressure Below Limit
T311
Supply Duct Static Pressure Above Limit
T312
Building Static Pressure Below Limit
T313
Building Static Pressure Above Limit
T314
IAQ Above Limit
A404
Fire Shut Down Emergency Mode (fire-smoke)
A405
Evacuation Emergency Mode
A406
Pressurization Emergency Mode
A407
Smoke Purge Emergency Mode
T408
Dirty Air Filter
A409
Supply Fan Status Failure
T409
Supply Fan Status Failure
T414
Loss of Communication with the Belimo Actuator
T414
Belimo Actuator Direction Error
T414
Belimo Actuator Failure
T414
Belimo Actuator Jammed
T414
Belimo Actuator Range Error
R-W1 Jumper Must Be Installed to Run Heat in Service
T420
Test
T421
Thermostat Y2 Input ON without Y1 ON
T422
Thermostat W2 Input ON without W1 ON
T423
Thermostat Y and W Inputs ON
T424
Thermostat G Input OFF on a Call for Cooling
T500
Current Sensor Board Failure - A1
T501
Current Sensor Board Failure - A2
T502
Current Sensor Board Failure - B1
T503
Current Sensor Board Failure - B2
A700
Supply Air Temperature Sensor Failure
T701
Staged Gas Thermistor 1 Failure
T702
Staged Gas Thermistor 2 Failure
T703
Staged Gas Thermistor 3 Failure
A704
Staged Gas Leaving Air Temp Sum Total Failure
T705
Limit Switch Thermistor Failure
LEGEND
A
— Alarm
P
— Pre-Alert
T
— Alert
DIAGNOSTIC ALARM CODES AND POSSIBLE CAUSES
T051, P051 (Circuit A, Compressor 1 Failure)
T052, P052 (Circuit A, Compressor 2 Failure)
T055, P055 (Circuit B, Compressor 1 Failure)
T056, P056 (Circuit B, Compressor 2 Failure) — Alert codes
051, 052, 055, and 056 are for compressors A1, A2, B1, and
B2 respectively. These alerts occur when the Current Sensor
(CS) does not detect compressor current during compressor
operation. When this occurs, the control turns off the compres-
sor and logs a strike for the respective circuit. These alerts reset
automatically.
If the current sensor board reads OFF while the compressor
relay has been commanded ON for a period of 4 continuous
seconds, an alert is generated.
Any time this alert occurs, a strike will be called out on the
affected compressor. If three successive strikes occur the
compressor will be locked out requiring a manual reset or
power reset of the circuit board. The clearing of strikes during
Table 105 — Alert and Alarm Codes (cont)
DESCRIPTION
ACTION TAKEN BY CONTROL
Stop cooling, but continue
to heat
Stop heating, but continue
to cool
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Alert
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Continue to run unit
Unit Shutdown
Run power exhaust
Run supply fan
Run supply and exhaust fans
Continue to run unit
Stop unit
Continue to run unit
Close economizer
Close economizer
Attempt to close economizer
Close economizer
Close economizer
No heat
Assume Y2 is Y1
Assume W2 is W1
Alert
Turn fan on
Stop compressor A1
Stop compressor A2
Stop compressor B1
Stop compressor B2
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
Stop staged gas heat
compressor operation is a combination of 3 complete cycles or
15 continuous minutes of run time operation. So, if there are
one or two strikes on the compressor and three short cycles
(ON-OFF, ON-OFF, ON-OFF) less than 15 minutes each
occur, the strikes will be reset to zero for the affected compres-
sor. Also, if the compressor turns on and runs for 15 minutes
straight with no compressor failure, the compressor's strikes
are cleared as well.
NOTE: Until the compressor is locked out, for the first two
strikes, the alert will not be broadcast to the network, nor will
the alarm relay be closed.
The possible causes are:
• High-pressure switch (HPS) open. The HPS-pressure
switch is wired in series with compressor relays on the
MBB. If the high-pressure switch opens during compressor
operation, the compressor stops, and the CS no longer
detects current, causing the control to activate this alert.
88
RESET
PROBABLE CAUSE
METHOD
Automatic
Outdoor dampers stuck, no load
Automatic
High load, dampers open
Dampers open, check configuration
Automatic
setpoint
Dampers open, check configuration
Automatic
setpoint
Dampers open, check configuration
Automatic
setpoint
Dampers open, check configuration
Automatic
setpoint
Automatic
Configuration error, or sensor error
Dampers open, check configuration
Automatic
setpoint
Automatic
VFD problem, broken fan belt
Automatic
VFD problem, broken fan belt
Automatic
Exhaust issues, check setpoint
Automatic
Exhaust issues, check setpoint
Automatic
Damper or IAQ control issues
Smoke detector switch or external
Automatic
switch
Automatic
Special fire mode control
Automatic
Special fire mode control
Automatic
Special fire mode control
Automatic
Dirty filter, switch setting
Automatic
Fan drive failure
Automatic
Fan drive failure, or sensor failure
Calibrate economizer, economizer
Automatic
failure, wiring
Automatic
Motor direction switch wrong, wiring
Automatic
Motor failure
Automatic
Obstruction in damper
Automatic
Calibrate economizer
Automatic
Add red wire jumpers
Automatic
Thermostat wiring error
Automatic
Thermostat wiring error
Automatic
Thermostat issues
Automatic
Thermostat or wiring issues
Automatic
Faulty board or wiring
Automatic
Faulty board or wiring
Automatic
Faulty board or wiring
Automatic
Faulty board or wiring
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty switch or wiring

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents