ITEM
DEHU
DEHUMIDIFICATION CONFIG.
→
D.SEL
Dehumidification Config
→
D.SEN
Dehumidification Sensor
→
D.EC.D
Econ disable in DH mode?
→
D.V.CF
Vent Reheat Setpt Select
→
D.V.RA
Vent Reheat RAT offset
→
D.V.HT
Vent Reheat Setpoint
→
D.C.SP
Dehumidify Cool Setpoint
→
D.RH.S
Dehumidify RH Setpoint
CCN
CCN CONFIGURATION
→
CCNA
CCN Address
→
CCNB
CCN Bus Number
→
BAUD
CCN Baud Rate
→
BROD
CCN BROADCST DEFINITIONS
→
→
BROD
TM.DT
CCN Time/Date Broadcast
→
→
BROD
OAT.B
CCN OAT Broadcast
→
→
BROD
ORH.B
CCN OARH Broadcast
→
→
BROD
OAQ.B
CCN OAQ Broadcast
→
→
BROD
G.S.B
Global Schedule Broadcst
→
→
BROD
B.ACK
CCN Broadcast Ack'er
→
SC.OV
CCN SCHEDULES-OVERRIDES
→
→
SC.OV
SCH.N
Schedule Number
→
→
SC.OV
HOL.T
Accept Global Holidays?
→
→
SC.OV
O.T.L.
Override Time Limit
→
→
SC.OV
OV.EX
Timed Override Hours
→
→
SC.OV
SPT.O
SPT Override Enabled ?
→
→
SC.OV
T58.O
T58 Override Enabled ?
→
→
SC.OV
GL.OV
Global Sched. Override ?
ALLM
ALERT LIMIT CONFIG.
→
SP.L.O
SPT lo alert limit/occ
→
SP.H.O
SPT hi alert limit/occ
→
SP.L.U
SPT lo alert limit/unocc
→
SP.H.U
SPT hi alert limit/unocc
→
SA.L.O
EDT lo alert limit/occ
→
SA.H.O
EDT hi alert limit/occ
→
SA.L.U
EDT lo alert limit/unocc
→
SA.H.U
EDT hi alert limit/unocc
→
RA.L.O
RAT lo alert limit/occ
→
RA.H.O
RAT hi alert limit/occ
→
RA.L.U
RAT lo alert limit/unocc
→
RA.H.U
RAT hi alert limit/unocc
→
R.RH.L
RARH low alert limit
→
R.RH.H
RARH high alert limit
→
SP.L
SP low alert limit
→
SP.H
SP high alert limit
→
BP.L
BP lo alert limit
→
BP.H
BP high alert limit
→
IAQ.H
IAQ high alert limit
TRIM
SENSOR TRIM CONFIG.
→
SAT.T
Air Temp Lvg SF Trim
→
RAT.T
RAT Trim
→
OAT.T
OAT Trim
→
SPT.T
SPT Trim
→
CTA.T
Cir A Sat.Cond.Temp Trim
→
CTB.T
Cir B Sat.Cond.Temp Trim
→
SP.A.T
Suct.Press.Circ.A Trim
→
SP.B.T
Suct.Press.Circ.B Trim
→
DP.A.T
Dis.Press.Circ.A Trim
→
DP.B.T
Dis.Press.Circ.B Trim
SW.LG
SWITCH LOGIC: NO / NC
→
FTS.L
Filter Status Inpt-Clean
→
IGC.L
IGC Feedback - Off
→
RMI.L
RemSw Off-Unoc-Strt-NoOv
→
ECS.L
Economizer Switch - No
→
SFS.L
Fan Status Sw. - Off
→
DL1.L
Dmd.Lmt.Sw.1 - Off
→
DL2.L
Dmd.Lmt.-Dehumid - Off
→
IAQ.L
IAQ Disc.Input - Low
→
FSD.L
Fire Shutdown - Off
→
PRS.L
Pressurization Sw. - Off
→
EVC.L
Evacuation Sw. - Off
→
PRG.L
Smoke Purge Sw. - Off
DISP
DISPLAY CONFIGURATION
→
TEST
Test Display LEDs
→
METR
Metric Display
→
LANG
Language Selection
→
PAS.E
Password Enable
→
PASS
Service Password
EXPANSION
0-2(multi-text strings)
1-2(multi-text strings)
Yes/No
0-1(multi-text strings)
0-8 ^F
55-95 dF
40-55 dF
10-90 %
1 - 239
0 - 239
1 - 5 (multi-text strings)
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
ON/OFF
0 - 99
YES/NO
0 - 4 HRS
0 - 4 HRS
YES/NO
YES/NO
YES/NO
–10-245 dF
–10-245 dF
–10-245 dF
–10-245 dF
–40-245 dF
–40-245 dF
–40-245 dF
–40-245 dF
–40-245 dF
–40-245 dF
–40-245 dF
–40-245 dF
0-100 %
0-100 %
0-5 "H2O
0-5 "H2O
–0.25-0.25 "H2O
–0.25-0.25 "H2O
0-5000
–10 - 10 ^F
–10 - 10 ^F
–10 - 10 ^F
–10 - 10 ^F
–30 - 30 ^F
–30 - 30 ^F
–50 - 50 PSIG
–50 - 50 PSIG
–50 - 50 PSIG
–50 - 50 PSIG
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
Open/Close
ON/OFF
ON/OFF
0-1(multi-text strings)
ENABLE/DISABLE
0000-9999
CL-4
RANGE
DEFAULT
Yes
On
Off
Off
Off
Off
Off
No
Yes
Yes
No
100
100
100
100
100
-0.25
0.25
1200
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Open
Off
Off
Enable
1111
ENTRY
0
1
0
0
70
45
55
1
0
3
1
1
0
60
85
45
40
40
60
90
40
0
0
2
0
0
0
0
0
0
0
0
0
0
0