Carrier 48AJ Operating And Service Manual page 87

Single package large rooftop units with scroll compressors and comfort link version 4.x controls
Table of Contents

Advertisement

ALARM OR
ALERT
NUMBER
A051
Circuit A, Compressor 1 Stuck On Failure
P051
Circuit A, Compressor 1 Failure
T051
Circuit A, Compressor 1 Failure
A052
Circuit A, Compressor 2 Stuck On Failure
P052
Circuit A, Compressor 2 Failure
T052
Circuit A, Compressor 2 Failure
A055
Circuit B, Compressor 1 Stuck On Failure
P055
Circuit B, Compressor 1 Failure
T055
Circuit B, Compressor 1 Failure
A056
Circuit B, Compressor 2 Stuck On Failure
P056
Circuit B, Compressor 2 Failure
T056
Circuit B, Compressor 2 Failure
T064
Circuit A Saturated Condensing Thermistor Failure
T065
Circuit B Saturated Condensing Thermistor Failure
T072
Evaporator Discharge Reset Sensor Failure
T073
Outside Air Temperature Thermistor Failure
T074
Space Temperature Thermistor Failure
T075
Return Air Thermistor Failure
T076
Outside Air Relative Humidity Sensor Failure
T078
Return Air Relative Humidity Sensor Failure
T082
Space Temperature Offset Sensor Failure
T090
Circuit A Discharge Pressure Transducer Failure
T091
Circuit B Discharge Pressure Transducer Failure
T092
Circuit A Suction Pressure Transducer Failure
T093
Circuit B Suction Pressure Transducer Failure
T110
Circuit A Loss of Charge
T111
Circuit B Loss of Charge
A120
Circuit A Low Saturated Suction Temperature Alarm.
P120
Circuit A Low Saturated Suction Temp-Comp A2 Shutdown
T120
Circuit A Low Saturated Suction Temperature Alert.
A121
Circuit B Low Saturated Suction Temperature Alarm.
P121
Circuit B Low Saturated Suction Temp-Comp B2 Shutdown
T121
Circuit B Low Saturated Suction Temperature Alert.
T122
Circuit A High Saturated Suction Temperature
T123
Circuit B High Saturated Suction Temperature
T126
Circuit A High Head Pressure
T127
Circuit B High Head Pressure
A140
Reverse Rotation Detected
A150
Unit is in Emergency Stop
T153
Real Time Clock Hardware Failure
A154
Serial EEPROM Hardware Failure
T155
Serial EEPROM Storage Failure Error
A156
Critical Serial EEPROM Storage Failure Error
A157
A/D Hardware Failure
A171
Staged Gas Control Board Comm Failure
A172
Controls Expansion Module Comm Failure
A173
ECB1 Board Communication Failure
A174
ECB2 Board Communication Failure
T177
4-20 MA Demand Limit Failure
T178
4-20 MA Static Pressure Reset/VFD Fail
A200
Linkage Timeout Error - Communication Failure
T210
Building Pressure Transducer Failure
T211
Static Pressure Transducer Failure
T220
Indoor Air Quality Sensor Failure
T221
Outdoor Air Quality Sensor Failure
T229
Economizer Minimum Position Override Input Failure
LEGEND
A — Alarm
P — Pre-Alert
T
— Alert
Table 105 — Alert and Alarm Codes
DESCRIPTION
ACTION TAKEN BY CONTROL
Turn off all compressors
Add strike to Compressor
Compressor locked off
Turn off all compressors
Add strike to Compressor
Compressor locked off
Turn off all compressors
Add strike to Compressor
Compressor locked off
Turn off all compressors
Add strike to Compressor
Compressor locked off
Use OAT for head pressure control
Use OAT for head pressure control
Unit Shutdown
Stop use of economizer
Unit Shutdown
Continue to run unit
Use OAT changeover control
Use differential drybulb changeover
Use Space temperature without offset
Stop circuit
Stop circuit
Stop circuit
Stop circuit
Stop circuit
Stop circuit
Stop circuit
Compressor A2 Shutdown
Stop circuit
Stop circuit
Compressor B2 Shutdown
Stop circuit
Stop circuit
Stop circuit
Stop circuit
Stop circuit
Stop unit
Stop unit
Stop unit
Stop unit
Stop unit
Stop unit
Stop unit
Stop gas heat
Stop options on CEM
Stop economizer & power exh
Stop unit
Stop demand limiting
Stop static pressure reset/VFD
Stop unit
Close economizer, stop exhaust
Stop unit
Stop IAQ control
Use a default value for IAQ
Use software configured
minimum
87
RESET
PROBABLE CAUSE
METHOD
Manual
Welded Contact
Automatic
High pressure switch, compressor
(max 3)
current, wiring error
Manual
Exceeded 3 strike limit
Manual
Welded Contact
Automatic
High pressure switch, compressor
(max 3)
current, wiring error
Manual
Exceeded 3 strike limit
Manual
Welded Contact
Automatic
High pressure switch, compressor
(max 3)
current, wiring error
Manual
Exceeded 3 strike limit
Manual
Welded Contact
Automatic
High pressure switch, compressor
(max 3)
current, wiring error
Manual
Exceeded 3 strike limit
Automatic
Faulty thermistor or wiring error
Automatic
Faulty thermistor or wiring error
Automatic
Faulty remote input on CEM board
Automatic
Faulty thermistor or wiring error
Automatic
Faulty thermistor or wiring error
Automatic
Faulty thermistor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor or wiring error
Automatic
Faulty sensor, wiring error
Automatic
Faulty sensor, wiring error
Automatic
Faulty sensor, wiring error
Automatic
Faulty sensor, wiring error
Manual
Low refrigerant charge
Manual
Low refrigerant charge
Low refrigerant charge, low airflow,
Manual
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
Automatic
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
Automatic
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
Manual
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
Automatic
dirty coil, broken fan belt, TXV
problem
Low refrigerant charge, low airflow,
Automatic
dirty coil, broken fan belt, TXV
problem
Manual
TXV problem
Manual
TXV problem
Dirty condenser, condenser fan
Automatic
failure
Dirty condenser, condenser fan
Automatic
failure
Manual
Incorrect Compressor Wiring
Manual
External shutdown command
Manual
Control Board failure, check lights
Manual
Control Board failure, check lights
Manual
Control Board failure, check lights
Manual
Control Board failure, check lights
Manual
Control Board failure, check lights
Automatic
Control Board failure, check lights
Automatic
Control Board failure, check lights
Automatic
Control Board failure, check lights
Automatic
Control Board failure, check lights
Automatic
Input failure, wiring error
Automatic
Input Failure, wiring error
Manual
Wiring errors, board failures
Automatic
Sensor failure, wiring error
Automatic
Sensor failure, wiring error
Automatic
Sensor failure, wiring error
Automatic
Sensor failure, wiring error
Automatic
Input failure, wiring error

Hide quick links: