Electra DELTA 22 Service Manual page 49

Indoor/outdoor unit, r410a
Table of Contents

Advertisement

1.3.4
Indoor unit diagnosis by MSMP and corrective actions
No.
Fault
1
Sensors failures of all
types
2
IPM Fault
3
Bad EEPROM
4
DC under/over Voltage
5
AC under Voltage
6
Indoor / Outdoor unit
Communication mismatch
7
No Communication
8
Compressor Lock
9
Bad Communication
1.4 Judgment by MegaTool
MegaTool is a special tool to monitor the system states.
Using MegaTool requires:
x A computer with RS232C port.
x A connection wire for MegaTool.
x A special MegaTool software.
Use MegaTool according to following procedure:
x Setup MegaTool software: copy the software to the computer.
x Connect RS232C port in computer with MegaTool port in Indoor/Outdoor unit controller by
the connection wire.
x Run the software and choose the COM port, you can monitor the A/C system state in monitor
tab.
1.5 Simple procedures for checking the Main Parts
1.5.1
Checking Mains Voltage.
Confirm that the Mains voltage is between 198 and 264 VAC. If Mains voltage is out of this range,
abnormal operation of the system is expected. If in range check the Power (Circuit) Breaker and
look for broken or loosed cable lugs or wiring mistake(s).
1.5.2
Checking Power Input.
If Indoor unit power LED is unlighted, power down the system and check the fuse of the Indoor unit. If the fuse
is OK replace the Indoor unit controller. If the fuse has blown, replace the fuse and power up again.
Checking Power Input procedure for the Outdoor unit is the same as with the Indoor unit.
SM DUO38 1-E.1 GB
Probable Cause
Electronics HW
problem
Electronics HW
problem
Indoor and Outdoor
controllers are with
different versions
Communication or
grounding wiring is not
good.
Communication quality is
low reliability
CONTENT
TROUBLESHOOTING
Corrective Action
Check sensors connections
or replace sensors.
Check all wiring and jumper
settings, if OK, replace
electronics.
No action, unless special
parameters are required for
unit operation.
Check outdoor unit power
supply voltage
Check outdoor unit power
supply voltage
Replace Indoor controller
Check Indoor to Outdoor
wiring and grounding
Switch unit to STBY and
restart
Check Indoor to Outdoor
wiring and grounding
12-5