[ IX Troubleshooting ]
[TKMU-A]
(2) Inverter output related troubles
Items to be checked
[1]
<P72 model>
Check the INV
(1) Remove power sup-
board error
ply.
detection cir-
cuit.
(2) Disconnect the invert-
er output wire from
the terminals of the
INV board (SC-U,
SC-V, SC-W).
(3) Apply power supply.
(4) Put the outdoor unit
into operation.
<P96, P120, P144
models>
(1) Remove power sup-
ply.
(2) Disconnect the invert-
er output wire from
the output terminals
(U, V, W) of the IPM.
(3) Apply power supply.
(4) Put the outdoor unit
into operation.
[2]
Disconnect the compres-
Check for
sor wiring, and check the
compressor
compressor Meg, and coil
ground fault or
resistance.
coil error.
HWE1116D
Phenomena
1)
IPM/overcurrent breaker trip
Error code: 4250
Detail code: No. 101, 104, 105, 106,
and 107
2)
Logic error
Error code: 4220
Detail code: No. 111
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
4)
IPM open
Error code: 5301
Detail code: No.119
1)
IPM/overcurrent breaker trip
Error code: 4250
Detail code: No. 101, 103, 104, 105,
106, and 107
2)
Logic error
Error code: 4220
Detail code: No. 111
3)
ACCT sensor circuit failure
Error code: 5301
Detail code: No.117
4)
DCCT sensor circuit failure
Error code: 5301
Detail code: No.118
5)
IPM open
Error code: 5301
Detail code: No.119
1)
Compressor Meg failure
Error if less than 1 Mohm.
When no liquid refrigerant in the
compressor
2)
Compressor coil resistance failure
Coil resistance value of 0.20 ohm
(20°C [68°F]) : P72 model
Coil resistance value of 0.092 ohm
(20°C [68°F]) : P96 - P144 models
- 312 -
Remedy
Replace the INV board.
Replace the INV board.
Replace the INV board.
Normal
See the section "Troubleshooting
the IPM" ( Refer toIX [4] -7- (6)).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
See the section "Troubleshooting
the IPM" ( Refer to IX [4] -7- (6)).
Replace the IPM, and put the out-
door unit back into operation.
If the problem persists, replace the
INV board.
Replace the INV board, and put
the outdoor unit back into opera-
tion.
If the problem persists, replace the
DCCT.
Replace the INV board.
Replace the DCCT board.
Replace the DCCT, and put the
outdoor unit back into operation.
If the problem persists, replace the
INV board.
Normal
Replace the compressor
Check that no liquid refrigerant in
the compressor.
GB