Mitsubishi Electric PURY-P72 Service Handbook page 320

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[ IX Troubleshooting ]
[TKMU-A]
Error display/failure condition
[1]
Inverter related errors
4250, 4255, 4256, 4220, 4225, 4226, 4230, 4240, 4260, 5301,
5305, 5306, 0403
[2]
Main power breaker trip
[3]
Main power earth leakage breaker trip
[4]
Only the compressor does not operate.
[5]
The compressor vibrates violently at all times or makes an abnor-
mal sound.
[6]
Only the fan motor does not operate.
[7]
The fan motor shakes violently at all times or makes an abnormal
sound.
[8]
Noise is picked up by the peripheral device
[9]
Sudden malfunction (as a result of external noise.)
HWE1116D
Measure/inspection item
Check the details of the inverter error in the error log at X LED Monitor
Display on the Outdoor Unit Board.
Take appropriate measures to the error code and the error details in ac-
cordance with IX [2] Responding to Error Display on the Remote Con-
troller.
<1> Check the breaker capacity.
<2> Check whether the electrical system is short-circuited or ground-
faulted.
<3> If items cause is not <1>or <2> are not the causes of the problem,
see (3)-[1].(page 316)
<1> Check the earth leakage breaker capacity and the sensitivity cur-
rent.
<2> Meg failure for electrical system other than the inverter
<3> If the cause is not <1>or <2>, see (3)-[1](page 316)
Check the inverter frequency on the LED monitor and proceed to (2) -
[4] if the compressor is in operation.(page 313)
See (2)-[4].(page 313)
Check the inverter frequency on the LED monitor and proceed to (2)-
[6], [7], [8] if the fan motor is in operation.(page 314)
Check the inverter frequency on the LED monitor and proceed to (2)-
[6], [7], [8] if the fan motor is in operation.(page 314)
<1> Check that power supply wiring of the peripheral device does not
run close to the power supply wiring of the outdoor unit.
<2> Check that the inverter output wiring is not in close contact with the
power supply wiring and the transmission lines.
<3> Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<4> Meg failure for electrical system other than the inverter
<5> Attach a ferrite core to the inverter output wiring. (Contact the fac-
tory for details of the service part settings.)
<6> Provide separate power supply to the air conditioner and other
electric appliances.
<7> If the error occurred suddenly, a ground fault of the inverter output
can be considered. See (2)-[4].(page 313)
*Contact the factory for cases other than those listed above.
<1> Check that the grounding work is performed properly.
<2>Check that the shielded wire is used as the transmission line when
it is required, and check that the grounding work is performed prop-
erly on the shielded wire.
<3>Check that neither the transmission line nor the external connec-
tion wiring does not run close to another power supply system or
does not run through the same conduit pipe.
* Contact the factory for cases other than those listed above.
- 311 -
GB