Mitsubishi Electric PURY-P72 Service Handbook page 148

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[ VII Control ]
(2) INV board
1) PURY-P72, P96, P120, P144YKMU-A
Functions are switched with the following connector.
Connector
CN6 short-
Enabling/disabling the following error
circuit con-
detection functions;
nector
ACCT sensor failure
(5301 Detail No. 115)
ACCT sensor circuit failure
(5301 Detail No.117)
IPM open/ACCT erroneous wiring
(5301 Detail No. 119)
Detection of ACCT erroneous wiring
(5301 Detail No.120)
ŒCN6 short-circuit connector is mated with the mating connector.
ŒLeave the short-circuit connector on the mating connector during normal operation to enable error detection and protect the
equipment from damage.
2) PURY-P72, P96, P120, P144TKMU-A
Switch
SW1
1
Enabling/disabling the following error
detection functions;
ACCT/DCCT sensor failure
(5301 Detail No. 115, 116)
ACCT/DCCT sensor circuit failure
(5301 Detail No.117,118)
IPM open/Disconnected CNCT2
(5301 Detail No. 119)
Detection of erroneous wiring
(5301 Detail No.120)
2
3
4
5
6
ŒAll are set to OFF at factory shipment. Unless otherwise specified, set the switch to OFF where indicated by "-," which may
be set to a certain setting for a reason.
ŒLeave SW1-1 to OFF during normal operation. If it is set to ON, errors cannot be detected and the unit may be damaged.
HWE1116D
Function according to connec-
Function
Enabled
Error detec-
tion enabled
Function according to switch
Function
Error detec-
tion enabled
-
-
-
-
-
- 139 -
tor
Disabled
Error detec-
Anytime after power on
tion disable
(No load op-
eration is pos-
sible.)
setting
OFF
ON
Error detec-
Anytime after power on
tion disable
(No load op-
eration is pos-
sible.)
-
-
-
-
-
-
-
-
-
-
Setting timing
Switch setting timing
-
-
-
-
-
-
-
-
-
-
GB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents