Mitsubishi Electric PURY-P72 Service Handbook page 189

Hide thumbs Also See for PURY-P72:
Table of Contents

Advertisement

[ VIII Test Run Mode ]
Model name of BC controller
Ambient
tempera-
ture
Indoor unit
Operating
conditions
Piping
Fan speed
Amount of refrigerant
Electric current
Outdoor
*1
Voltage
unit
Compressor frequency
Indoor unit
LEV open-
ing
BC controller (1/2/3)
High pressure(63HS1)/
Low pressure(63LS)
Pressure
BC controller on the liquid side(PS1)/
Intermediate part(PS3)
Outdoor
unit
Temp. of
each sec-
tion
Indoor unit
*1. Measurements of current and voltage that are listed in the table above are those of the TKMU model.
HWE1116D
Operation
Indoor
DB/WB
Outdoor
No. of connected units
No. of units in operation
Model
Main pipe
Branch pipe
Total pipe length
[lbs-oz]
*1
Pulse
Discharge (TH4)
Heat exchanger outlet
(TH3)
Accumulator inlet
Accumulator outlet
Compressor inlet
Compressor shell bottom
LEV inlet
Heat exchanger inlet
- 180 -
Outdoor unit model
PURY-P168T(Y)SKMU-A
PURY-P96T(Y)KMU-A
CMB-P108NU-GA
26.7°C/19.4°C [80 °F/67 °F]
35°C/í [95 °F/í]
Unit
-
30/30/36/36/36
m
[ft]
-
kg
A
V
Hz
61
230/230/275/275/275
2000/2000/260
2.78/0.91
[403/131]
MPa
[psi]
87 [189]
41 [106]
8 [46]
°C
8 [46]
[°F]
19 [66]
40 [104]
PURY-P72T(Y)KMU-A
5
5
5 [16-3/8"]
10 [32-3/4"]
55 [180-1/8"]
Hi
37.9 [83-9]
38.6
230
43
2.65/0.91
[384/131]
2.65/2.65
[384/384]
76 [169]
41 [106]
14 [57]
14 [57]
23 [73]
34 [93]
22 [72]
9 [48]
GB