[ IX Troubleshooting ]
LEV
-5- LEV
LEV operation
LEV are stepping-motor-driven valves that operate by receiving the pulse signals from the indoor and outdoor unit control
boards.
(1) Outdoor LEV (LEV5a,b), Indoor LEV and BC controller LEV
The valve opening changes according to the number of pulses.
1) Control board and LEVs (Indoor unit LEV; BC controller LEV1 (type G1 only) and LEV3)
LEV
Blue
4
Brown
M
6
Yellow
2
5
1
White
Red Orange
Note. The connector numbers on the intermediate connector and the connector on the control board differ. Check the color of the lead wire
to judge the number.
2) Control board and LEV (BC controller LEV1 (types GA1 and HA1 only))
LEV
Blue
4
red
6
M
Yellow
2
5
1
3
White
Orange
3) Pulse signal output and valve operation
Output
(phase)
number
1
1
ON
2
ON
3
OFF
4
OFF
HWE1116D
Intermediate connector
2
5
1
4
3
3
2
4
6
1
4
3
2
1
Output state
2
3
4
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
- 296 -
Outdoor control board
Brown
6
Red
5
Blue
4
Orange
3
Yellow
2
White
1
Connector
Indoor unit connector CN60
Control board CNLV1,CNLV2
Outdoor control board
red
6
5
Blue
4
Orange
3
Yellow
2
White
1
Output pulses change in the following orders when the
Valve is closed; 1
2
Valve is open;
4
3
*1. When the LEV opening angle does not change,
all the output phases will be off.
*2. When the output is open phase or remains ON,
the motor cannot run smoothly, and rattles and vibrates.
DC12V
Drive circuit
4
3
2
1
DC12V
Drive circuit
4
3
2
1
3
4
1
2
1
4
GB