Console Control; 3: Address Assignment; Remote Microphone / Operator Console Address Assignments - Fire-Lite ECC-50 Instruction Manual

Emergency command center
Table of Contents

Advertisement

Main Menu - User Programming
Aux Power Selects whether this power is Constant or Resettable use from TB17.
Speaker Volume Control NAC If the Cooper Wheelock SP-SVC module is installed on TB23
of the main control board, allowing manual volume setting for telephone paging and background
music for a specific speaker or speaker zone, select Enabled.

Console Control

Console Priority Priority can be assigned to the operator consoles so that the primary operator
interface can always override the functions at the local operator consoles or remote microphones.
Select POC->LOC->RM for console priority. Selecting Equal for priority allows users with access
to the system on a a "first come, first served" basis.
Device Control Timeout Enter the maximum amount of time (30-300 seconds) that one of the
devices (Primary Operator Console, Local Operator Console, Remote Page Unit, or Remote Micro-
phone) can remain in manual control of the ECC system.
Paging Timeout Enter the maximum amount of time (30-300 seconds) that the microphone's
PTT switch can be held.
3.1.3 Address Assignment

Remote Microphone / Operator Console Address Assignments

Any combination of up to eight (8) remote consoles (ECC-LOC, ECC-RPU, and ECC-RM) can be
used in the system. Odd numbered addresses are not selectable. Addresses must be sequential,
even numbers. Identify which consoles are installed at addresses 4, 6, 8, 10, 12, 14, 16, and 18 as
either Local Operator Console or Remote Microphone. Note that the ECC-RPU and ECC-RM are
both considered remote microphones. Refer to Section 2.14, "Addressing External Data Bus
Devices" for information on dipswitch settings.
Emergency Command Center Manual — P/N LS10001-000FL-E:D 9/3/2014
Strobe Manufacturer
Gentex
Table 3.1 Maximum Number of Strobes by Manufacturer
Figure 3.5 Console Control
Figure 3.6 RM/Console Address Assignments
Maximum Number of Strobes
26
Programming
63

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecc-100Ecc-50eEcc-100e

Table of Contents