3.1 Main Menu - User Programming

This screen shows the main menu for the ECC user programming options. Changes to program-
ming require a valid password for system login. Note that a password is NOT required to change
the date/time, view the informational screens, or view the panel history.
3.1.1 Password Options
Changes to ECC programming require a valid password login. Programming changes cannot be
made when there is an active event in the system.
Log In Password The default password for the ECC-50/100 is 0000.
New Password It is recommended that the password be changed to increase system security.
Valid passwords contain four digits from 0000-9999.
Verify New Password Re-enter the new password for confirmation.
Inactivity Timeout Select the amount of time, 5 minutes, 10 minutes, 20 minutes, 30 minutes, or
60 minutes, the system is allowed to remain idle before automatic user log out. The timeout feature
helps the system protect against unauthorized programming changes.
60
Figure 3.1 Main Menu
Figure 3.2 Password Options