7.7.2
To change the 60/100 concentric
connection to a dual pipe connection
The  concentric  connection  can  be  changed  from  Ø60/100  to
Ø80/125 by an adapter set.
1 Remove the concentric pipe from the air supply and combustion
gas  pipe  at  the  top  of  the  gas  boiler  by  turning
counterclockwise.
2 Remove the O­ring from the concentric pipe and fit it around the
flange of the dual pipe adapter Ø80.
3 Place  the  combustion  gas  connection  (Ø80)  in  the  top  of  the
appliance and turn it clockwise so that the measurement nipple
points  straight  forward.  The  integral  sealing  ring  ensures  an
airtight connection.
4 Remove  the  lid  from  the  air  supply  connection.  Make  sure  to
properly connect the air intake. Room air dependent installation
is NOT allowed.
5 Check  the  connection  of  the  internal  flue  pipe  and  the
condensate collector. Make sure it is properly connected.
EHYKOMB33AA
Daikin Altherma hybrid heat pump – gas boiler module
4P353067­1A – 2013.10
7.7.3
Calculate the total piping length
When  the  resistance  of  the  flue  pipe  and  air  supply  pipe  increase,
the  appliance  power  will  decrease.  The  maximum  permitted
reduction in power is 5%.
The  resistance  of  the  air  supply  pipe  and  combustion  gas  flue
depends on:
▪ the length,
▪ the diameter,
▪ all components (bends, elbows,...).
The total permitted pipe length of the air supply and the combustion
gas  flue  is  indicated  for  each  appliance  category.  For  dual  pipe
connection, the indication of pipe length is based on Ø80 mm.
Equivalent length
R/D=1
Bend 90°
Bend 45°
R/D=0.5
Elbow 90°
Elbow 45°
R/D=1
D
For a dual pipe connection, all defined lengths assume a diameter of
80 mm. In case of smaller or larger pipe diameters, the permissible
pipe  length  is  respectively  smaller  or  larger.  In  case  of  smaller
diameter, the following applies:
▪ Ø70: 0.59 × the permissible pipe length for Ø80
▪ Ø60: 0.32 × the permissible pipe length for Ø80
▪ Ø50: 0.15 × the permissible pipe length for Ø80
Contact the manufacturer to check the calculations for the resistance
of  the  air  supply  and  combustion  gas  flue  pipe  and  the  wall
temperature at the end of the combustion gas flue pipe.
7 Installation
Length
2 m
1 m
4 m
2 m
R/D=0.5
D
Installation and operation manual
17