Additional Refrigerant Charge - koppel KV24ODU-ARF21 Service Manual

Four-way ceiling cassette/ceiling-floor mount: convertible/universal outdoor unit
Table of Contents

Advertisement

3.

Additional Refrigerant Charge

Caution:
a)
Refrigerant cannot be charged until field wiring has been completed.
b)
Refrigerant may only be charged after performing the leak test and the vacuum pumping.
c)
When charging a system, care shall be taken that its maximum permissible charge is never exceeded, in view of the danger of liquid
hammer.
d)
Charging with an unsuitable substance may cause explosions and accidents, so always ensure that the appropriate refrigerant is
charged.
e)
Refrigerant containers shall be opened slowly.
f)
Always use protective gloves and protect your eyes when charging refrigerant.
The outdoor unit is factory charged with refrigerant. Calculate the added refrigerant according to the diameter and the length of the liquid side
pipe of the outdoor unit/indoor unit.
R(g)
D(mm)
L(m)
Less than 5m (One-way)
Added Refrigerant When
Over 5m(One-way)
Remark:
R (g): Additional refrigerant to be charged
L (m): The length of the refrigerant pipe (one-way)
D (mm): Liquid side piping diameter
φ6.4
11g/m×(L-5)
Φ9.5
30g/m×(L-5)
Test Operation
Φ12.7
60g/m×(L-5)
67