Rinnai RU80i Installation And Operation Manual page 38

Direct vent tankless water heater
Hide thumbs Also See for RU80i:
Table of Contents

Advertisement

Available languages

Available languages

 
Code 
Defini on 
19 
Electrical Grounding  
25  
Condensate Trap is full 
31 
Burner Sensor 
Outgoing Water 
32 
Temperature Sensor  
Heat Exchanger Outgoing 
33 
Temperature Sensor 
Outside Temperature 
41 
Sensor 
Inlet Water Temperature 
51 
Sensor 
Modula ng Solenoid Valve 
52 
Signal 
57 
Burner 
58 
Secondary heat exchanger 
61 
Combus on Fan 
65 
Water Flow Control 
70 
PC Board 
71 
Solenoid Valve Circuit 
72 
Flame Sensing Device 
73 
Burner Sensor Circuit 
79 
Water Leakage Detected 
Scale Build‐up in Heat 
LC # 
Exchanger (when checking 
(LC0, 
maintenance code history, 
LC1, 
"00" is subs tuted for 
LC2,...) 
"LC")  
Maintenance has been 
FF 
performed 
No 
Nothing happens when 
code  
water flow is ac vated.  
38 
 
Remedy 
licensed 
professional 
Check all components for electrical short. 
 
only 
 
Check condensate trap and drain line for blockage. 
Replace condensate trap. 
Measure resistance of sensor.   
Replace sensor. 
Check sensor wiring for damage. 
Measure resistance of sensor. 
Clean sensor of scale build‐up. 
Replace sensor.  
Check modula ng gas solenoid valve wiring harness for loose or damaged terminals. 
Measure resistance of valve coil. 
Contact a licensed professional. 
There is scale build up in the secondary heat exchanger and it needs to be flushed to prevent 
damage.  Refer to the flushing instruc ons in the manual.  Hard water must be treated to 
prevent scale build up or damage to the heat exchanger. 
licensed 
Ensure fan will turn freely. 
professional 
Check wiring harness to motor for damaged and/or loose connec ons. 
 
only   
Measure resistance of motor winding. 
The water flow control valve has failed to close during the bath fill func on.  Immediately turn 
off the water and discon nue the bath fill func on.  Contact a licensed professional to service 
the appliance. 
Check PC board DIP switches for correct posi on.  
Check the connec on harness at the connec on on the PC board.   
Replace PC board. 
Replace the PC Board. 
Verify flame rod is touching flame when unit fires. 
Check all wiring to flame rod. 
Remove flame rod and check for carbon build‐up; clean with sand paper. 
Check inside burner chamber for any foreign material blocking flame at flame rod. 
Measure micro amp output of sensor circuit with flame present. 
Replace flame rod. 
Check sensor wiring and PC board to be sure that they have not been damaged. 
Replace sensor. 
Turn off water supply and contact licensed professional. 
LC0~LC9 indicates that there is scale build up in the heat exchanger and that the heat 
exchanger needs to be flushed to prevent damage.  Refer to the flushing instruc ons in the 
manual.  Hard water must be treated to prevent scale build up or damage to the heat 
exchanger. 
 
To operate the water heater temporarily un l the heat exchanger can be flushed, push the On/
Off bu on on the temperature controller 5  mes.  Repeated LC codes will eventually lockout 
the water heater. 
Please call Rinnai technical department. 
 
Indicates a licensed professional performed maintenance or corrected an issue. 
Clean inlet water supply filter. 
 
On new installa ons ensure hot and cold water lines are not reversed. 
Verify you have at least the minimum flow rate required to fire unit. 
Check for cold to hot cross over. Isolate circula ng system if present.  Turn off cold water to the 
unit, open pressure relief valve; if water con nues to flow, there is bleed over in your plumbing. 
licensed 
Verify turbine spins freely. 
professional 
Measure the resistance of the water flow control sensor. 
only 
If the display is blank and clicking is coming from the unit, disconnect the water flow servo 
motor (GY, BR, O, W, P, BL, R).  If the display comes on replace the water flow servo motor. 