PennBarry Breezeway User Manual

PennBarry Breezeway User Manual

Wall mounted propeller fans direct drive and belt drive

Advertisement

Bulletin BZW05
BREEZEWAY
Wall Mounted Propeller Fans
Direct Drive and Belt Drive

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Breezeway and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for PennBarry Breezeway

  • Page 1 Bulletin BZW05 BREEZEWAY Wall Mounted Propeller Fans Direct Drive and Belt Drive...
  • Page 2: Table Of Contents

    We reserve the right to make changes at any time, without notice, to models, specifi cations, options, availability, etc. This bulletin illustrates the appearance of PennBarry products at the time of publication and we reserve the right to make changes in design and construction at anytime without notice.
  • Page 3: General Information

    General Information Breezeway The Breezeway propeller fan line provides a variety of solutions BELT DRIVE to address the needs of wall mounted exhaust and ventilation BLL – An economical product designed applications such as garages, factories, warehouses and other for applications through 14,000 CFM relatively clean air applications.
  • Page 4: Options And Accessories

    Options and Accessories Breezeway PennBarry provides a wide variety of accessories for the Breezeway propeller fan line. The components shown below can be mixed and matched to suit the demands of the particular application. WEATHERSHIELD GUARD WALL PANEL WEATHERSHIELD SHUTTER...
  • Page 5 Options and Accessories Breezeway Rear and Front Guards Protection is available for both the rear motor side (rear guard) of the fan and the front face (front guard) of the fan. Both assemblies include a sheet metal sleeve with an attached guard.
  • Page 6 3. Mounting Holes 4. Motor Mounting Assembly Caution: When a Breezeway fan is selected for a supply application, fan velocities greater than 500 FPM can pull water into the structure. We suggest that a PennBarry Weathershield be 3"...
  • Page 7 Options and Accessories Breezeway Wall Sleeves Wall Sleeves effectively add depth to the wall where the fan and several of its accessories will be installed. This provides more fl exibility and convenience MIN. to secure these parts, as well as protection and a neat appearance. Standard construction is galvanized steel.
  • Page 8 Provides a ventilation package in one convenient and compact Wall Galv. Steel Sleeve with Type P Direct assembly. The Fan Pak incorporates the Breezeway Type P Drive Fan and Integral Rear Guard direct drive fans with their integral back guards installed in a galvanized steel sleeve with a self-acting shutter on the exterior face.
  • Page 9: Motor Selection

    Then determine the frequency. Is it 60 Hz or 50 Hz? Variable Speed Motor Control Environmental Considerations PennBarry Lek-Trol™ solid state controllers are an economical Most clean air fan applications utilize Open Drip-Proof way to reduce the high speed of selected P Series motors (ODP) motors.
  • Page 10 Motor Selection Breezeway P Series Direct Drive Motor Availability ™ and Lek-Trol Controller Availability NOMINAL RPM 115/1/60 ODP 230/1/60 ODP TE 115/200/240/1 MODEL 1050 1300 1550 1650 AVAIL LEK-TROL AVAIL LEK-TROL AVAIL LEK-TROL P10VA 1/30 LT30 P10RA 1/12 LT30 USE TE...
  • Page 11 It is also important that ambient temperatures of the area in which the motor control is located be taken into consideration when making heater selections. Ambient compensated overload relays are available for abnormal temperature conditions. PENNBARRY...
  • Page 12: Direct Drive Dimensional Data

    23 3/4 BX20Q 20 3/4 12 1/2 23 3/4 BX24T 24 3/4 13 1/2 27 3/4 BX24Q 24 3/4 13 1/8 27 3/4 MAX. BREEZEWAY BC Dimensional Data BC24-42 WALL APPROX. PANEL MODEL DIA. MAX. MAX. OPENING SHIP WT. GAUGE GAUGE (LBS.)
  • Page 13: Performance Data

    Direct Drive Fan Data Breezeway P Series Features: • Exhaust or supply • Continuous duty, PSC motors • Zinc-coated wire guard designed to OSHA specifi cations • Integral spun steel venturi with welded corners • Statically and dynamically balanced, die-formed aluminum propeller with steel hub •...
  • Page 14 Note: Breezeway fans are only one component of a total The direct drive performance chart on the previous page system. As such, fan performance is directly affected by the provides the tabular data (CFM and static pressure) used to system.
  • Page 15 Direct Drive Fan Data Breezeway Breezex Reversible Fan Features: • Field reversible supply and exhaust • Includes Reversing Switch (TE, 115V/1PH/60HZ only) • Totally Enclosed (TE) Motor or Explosion Proof motors available (Check Motor Availability Chart – Page 9) • Integral Thermal Overload Protection •...
  • Page 16 Direct Drive Fan Data Breezeway BC Cast Aluminum Propeller Fan Features: • Exhaust or supply • Fabricated steel power assembly • Statically and dynamically balanced, heavy duty cast aluminum propeller with taper lock hub • Integral spun steel venturi with welded corners •...
  • Page 17: Belt Drive Dimensional Data

    Belt Drive Dimensional Data Breezeway MODEL BLL MODEL BCH DIA. MAX. Dimensions Dimensions DIA. MAX. MODEL DIA. MAX. MODEL BCH24 BLL24 BCH30 2 1/2 BLL30 2 1/2 BCH36 4 3/4 BLL36 4 3/4 BCH42 3 3/4 4 1/2 BCH48 2 3/4...
  • Page 18 0.3 0.4 0.6 0.8 1 8 10 Note: Breezeway fans are only one component of a total system. As such, Motor Power Output (BHP) performance is directly affected by the system. It is critical that system designers determine actual system losses to ensure that the actual fl ow is specifi ed in the system range.
  • Page 19: Bll

    BLL 24 - Belt Drive Fan Data Breezeway 1.500 1.400 Do not select shaded area. 1.300 1.200 1.100 1.000 0.900 0.800 0.700 0.600 0.500 0.400 0.300 0.200 0.100 0.000 Carbon Steel Panel = 16 gauge Wall Opening = 28 3/4 in.sq.
  • Page 20 Belt Drive Fan Data - BLL 30 Breezeway 0.800 Do not select shaded area. 0.700 0.600 0.500 0.400 0.300 0.200 0.100 0.000 Carbon Steel Panel = 16 gauge Wall Opening = 34 3/4 in.sq. Peak BHP = (RPM/741)^3 2000 4000...
  • Page 21 BLL 36 - Belt Drive Fan Data Breezeway 0.700 Do not select shaded area. 0.600 0.500 0.400 0.300 0.200 0.100 0.000 Carbon Steel Panel = 16 gauge Wall Opening = 40 3/4 in.sq. Peak BHP = (RPM/526)^3 2000 4000 6000...
  • Page 22 Belt Drive Fan Data - BHM 24B Breezeway 1.000 Do not select shaded area. 0.875 0.750 0.625 0.500 0.375 0.250 0.125 0.000 Galv. Panel = 16 gauge Wall Opening = 32 3/4 in.sq. Peak BHP = (RPM/934)^3 1000 2000 3000...
  • Page 23 BHH 24B - Belt Drive Fan Data Breezeway 1.000 0.900 Do not select shaded area. 0.800 0.700 0.600 0.500 0.400 0.300 0.200 0.100 0.000 2000 4000 6000 8000 10000 12000 AIR FLOW - CFM Galv. Panel = 16 gauge Wall Opening = 32 3/4 in.sq.
  • Page 24 Belt Drive Fan Data - BHM 30B Breezeway 1.200 Do not select shaded area. 1.000 0.800 0.600 0.400 0.200 0.000 2000 4000 6000 8000 10000 12000 14000 16000 AIR FLOW - CFM Galv. Panel = 16 gauge Wall Opening = 38 3/4 in.sq.
  • Page 25 BHH 30B - Belt Drive Fan Data Breezeway 1.500 Do not select shaded area. 1.250 1.000 0.750 0.500 0.250 0.000 2000 4000 6000 8000 10000 12000 14000 16000 18000 AIR FLOW - CFM Galv. Panel = 16 gauge Wall Opening = 38 3/4 in.sq.
  • Page 26 Belt Drive Fan Data - BHM 36B Breezeway 0.750 Do not select shaded area. 0.625 0.500 0.375 0.250 0.125 0.000 4000 8000 12000 16000 20000 AIR FLOW - CFM Galv. Panel = 14 gauge Wall Opening = 44 3/4 in.sq.
  • Page 27 BHH 36B - Belt Drive Fan Data Breezeway 1.500 Do not select shaded area. 1.250 1.000 0.750 0.500 0.250 0.000 4000 8000 12000 16000 20000 24000 28000 AIR FLOW - CFM Galv. Panel = 14 gauge Wall Opening = 44 3/4 in.sq.
  • Page 28 Belt Drive Fan Data - BHM 42B Breezeway 0.750 Do not select shaded area. 0.625 0.500 0.375 0.250 0.125 0.000 4000 8000 12000 16000 20000 24000 28000 AIR FLOW - CFM Galv. Panel = 14 gauge Wall Opening = 50 3/4 in.sq.
  • Page 29 BHH 42B - Belt Drive Fan Data Breezeway 1.200 Do not select shaded area. 1.000 0.800 0.600 0.400 0.200 0.000 5000 10000 15000 20000 25000 30000 35000 AIR FLOW - CFM Galv. Panel = 14 gauge Wall Opening = 50 3/4 in.sq.
  • Page 30 Belt Drive Fan Data - BHM 48B Breezeway 0.500 Do not select shaded area. 0.375 0.250 0.125 0.000 5000 10000 15000 20000 25000 30000 35000 AIR FLOW - CFM Galv. Panel = 14 gauge Wall Opening = 57 in.sq. Peak BHP = (RPM/298)^3 Galv.
  • Page 31 BHH 48B - Belt Drive Fan Data Breezeway 1.000 Do not select shaded area. 0.875 0.750 0.625 0.500 0.375 0.250 0.125 0.000 10000 20000 30000 40000 50000 AIR FLOW - CFM Galv. Panel = 14 gauge Wall Opening = 57 in.sq.
  • Page 32 Belt Drive Fan Data - BHH 54B Breezeway 2.000 Do not select shaded area. 1.750 1.500 1.250 1.000 0.750 0.500 0.250 Galv. Panel = 14 gauge Wall Opening = 63 in.sq. Peak BHP = (RPM/273)^3 0.000 10000 20000 30000 40000 50000 Galv.
  • Page 33 BHH 60B - Belt Drive Fan Data Breezeway 1.750 Do not select shaded area. 1.500 1.250 1.000 0.750 0.500 0.250 Galv. Panel = 14 gauge Wall Opening = 69 in.sq. Peak BHP = (RPM/240)^3 0.000 Galv. Mtr. Plate = 10 gauge Est.
  • Page 34 Belt Drive Fan Data - BCH 24 Breezeway 2.400 Do not select shaded area. 2.000 1.600 1.200 0.800 0.400 Carbon Steel Panel = 16 gauge Wall Opening = 28 3/4 in.sq. Peak BHP = (RPM/1108)^3 0.000 2000 4000 6000 8000 10000 Carbon Stl.
  • Page 35: Bch

    BCH 30 - Belt Drive Fan Data Breezeway 2.400 2.200 Do not select shaded area. 2.000 1.800 1.600 1.400 1.200 1.000 0.800 0.600 0.400 0.200 Carbon Steel Panel = 16 gauge Wall Opening = 34 3/4 in.sq. Peak BHP = (RPM/877)^3 0.000...
  • Page 36 Belt Drive Fan Data - BCH 36 Breezeway 2.400 2.200 Do not select shaded area. 2.000 1.800 1.600 1.400 1.200 1.000 0.800 0.600 0.400 0.200 0.000 Carbon Steel Panel = 16 gauge Wall Opening = 40 3/4 in.sq. Peak BHP = (RPM/676)^3...
  • Page 37 BCH 42 - Belt Drive Fan Data Breezeway 2.400 2.200 Do not select shaded area. 2.000 1.800 1.600 1.400 1.200 1.000 0.800 0.600 0.400 0.200 Carbon Steel Panel = 16 gauge Wall Opening = 46 3/4 in.sq. Peak BHP = (RPM/676)^3 0.000...
  • Page 38 Belt Drive Fan Data - BCH 48 Breezeway 2.400 2.200 Do not select shaded area. 2.000 1.800 1.600 1.400 1.200 1.000 0.800 0.600 0.400 0.200 Carbon Steel Panel = 16 gauge Wall Opening = 55 in.sq. Peak BHP = (RPM/555)^3 0.000...
  • Page 39 BCH 54 - Belt Drive Fan Data Breezeway 2.600 2.400 Do not select shaded area. 2.200 2.000 1.800 1.600 1.400 1.200 1.000 0.800 0.600 0.400 0.200 0.000 Carbon Steel Panel = 16 gauge Wall Opening = 61 in.sq. Peak BHP = (RPM/416)^3...
  • Page 40 Belt Drive Fan Data - BCH 60 Breezeway 3.200 3.000 Do not select shaded area. 2.800 2.600 2.400 2.200 2.000 1.800 1.600 1.400 1.200 1.000 0.800 0.600 0.400 0.200 0.000 Carbon Steel Panel = 16 gauge Wall Opening = 67 in.sq.
  • Page 41: Sound Data Notes

    AMCA Publication 303 and the ASHRAE Guides Sone Ratings provide more information on this process. Another typical In addition to sound power levels, PennBarry has provided application of sound power levels is to compare similar fans. sone ratings to allow designers to make an educated judgment Generally differences of 6 dB in the 63 Hz band and 3 dB in as to the noise level a fan will develop in a space.
  • Page 42: Engineering Notes

    Interaction of Fan Curves and System Curves The following section includes engineering and technical data, A ventilation system using a Breezeway may consist of a fan guidelines and system explanations related to air moving with duct connected to the inlet side. Control dampers, grilles, and control devices.
  • Page 43 Engineering Notes Breezeway If the system resistance has been underestimated, then fan damper is part of external static pressure, and should be curves and system curves will not intersect at the system accounted for when estimating system static pressure. Use design point.
  • Page 44 Metric Equivalents Many PennBarry products are specifi ed and installed overseas. For your convenience, the table below provides conversion factors from English to Metric. AMCA STANDARD /...
  • Page 45: Sample Specifi Cations

    Licensed Ratings Seal for Air and Sound Performance, and Type BLL shall be UL and CSA Listed. Belt driven Axial Panel exhaust fan shall be Breezeway BLL Type BCH manufactured by PennBarry, Richardson, Texas. A heavy Belt driven Axial Panel exhaust fan shall be Breezeway BCH gauge motor mounting platform is supported by formed manufactured by PennBarry, Richardson, Texas.
  • Page 46: One Year Limited Warranty

    Product; repair or replace (without removal or installation) the entire defective PennBarry Product; or refund the invoiced price of the PennBarry Product. In all cases, a reasonable time period must be allowed for warranty repairs to be completed. What You Must Do In order to make a claim under these warranties: 1.
  • Page 47 Inline Fans Powered Airette Airette Domex Axial Axcentrix Axial Roof Ventilators Gravity Intake/Relief Hood Bifurcator Fan Axial Roof Ventilators For more information contact your local PennBarry Sales Manufacturer Representative or visit us at www.PennBarry.com ©2005 PennBarry™ All Rights Reserved. February 2005...

Table of Contents