7.3

Error messages

Display
Error 1
Cover open
Error message is displayed
until the carriage is inserted
correctly and locked.
Cause:
Action/Remedy: Correctly insert the carriage and flap down the handle.
Error 2
Max Niveau
Error message is displayed
until reset.
Cause:
Action/Remedy: PH15: Remove the tank immediately. Check/clean filler neck, tank cap and level regulating
Error 3
Filltime
Error message is displayed
until reset.
Note:
Cause:
Action/Remedy: open shut-off valve in the water supply line. Clean water filter (see chapter 6.3). Check/replace
Error 4
No signal
Error message is alternating
with the standard operating
display.
Cause:
Action/Remedy: Replace the battery of the radio humidity
Error 5
Leakage sensor
Error message is displayed
until reset.
Cause:
Action/Remedy: PH15: Check/clean filler neck, tank cap and level regulating valve in tank cap (replace tank
green LED
flashes
Carriage not inserted and locked.
flashes
Maximum water level in the base tub exceeded. Safety switch has triggered.
PH15: water tank not tight (tank cap not tight and/or level regulating valve in the tank cap
blocked or defective).
PH15A: inlet valve defective.
valve in tank cap (replace tank cap if necessary), then close tank cap correctly.
PH15A: check/replace inlet valve.
flashes
This message is displayed only on the
Shut-off valve in the water supply line closed. Internal water filter (near to the inlet valve)
blocked. Inlet valve defective.
inlet valve.
flashes
The
Defensor PH15/PH15A does not receive any signal from the radio humidity sensor
tion). Battery of the radio humidity sensor
Radio humidity
sensor installed outside the signal range of 25 m.
Note: As long as the unit does not receive any signal from the radio humidity sensor
to the internal
humidity
sensor.
radio humidity sensor
inside the signal range.
flashes
PH15: Water tank not tight (tank cap not tight and/or level regulating valve in the tank cap
blocked or defective). Unit is not placed on a horizontal surface. Safety switch defective.
PH15A: Inlet valve defective. Level switch defective. Safety switch defective.
cap if necessary) , then close tank cap correctly. Place unit on a horizontal surface. Check/
replace safety switch.
PH15A: Check/replace inlet valve. Check/replace level switch. Check/replace safety
switch.
Buzzer
Error relay
–––
activated
buzzes loudly
activated
(can not be
switched off)
buzzes
activated
Defensor
PH15A
beeps briefly
activated
every 6 min-
utes
soon empty or
radio humidity
sensor. Check/replace
buzzes loudly
activated
(can not be
switched off)
Resetting
Automatic resetting as
soon as the carriage is
inserted correctly and
locked.
Switch unit off, then on
again.
Switch unit off, then on
again.
Automatic resetting as
soon as the unit re-
ceives a signal from the
radio humidity
sensor.
(op-
sensor defective.
it switches
radio humidity
sensor. Install
Switch unit off, then on
again.