6. Maintain level tolerance to 1/2 inch maximum
across the entire length or width of the unit.
Excessive exposure of this furnace to contami-
nated combustion air may result in equipment
damage or personal injury. Typical contami-
nates include: permanent wave solutions, chlo-
rinated waxes and cleaners, chlorine based
swimming pool chemicals, water softening
chemicals, carbon tetrachloride, Halogen type
refrigerants, cleaning solvents (e.g. perchloro-
ethylene), printing inks, paint removers, var-
nishes, hydrochloric acid, cements and glues,
antistatic fabric softeners for clothes dryers,
masonry acid washing materials.
If a unit is to be installed on a roof curb or special frame
other than a YORK roof curb, gasketing must be
applied to all surfaces that come in contact with the unit
underside.

RIGGING AND HANDLING

Exercise care when moving the unit. Do not remove
any packaging until the unit is near the place of installa-
tion. Rig the unit by attaching chain or cable slings to
the round lifting holes provided in the base rails.
Spreaders, whose length exceeds the largest dimen-
sion across the unit, MUST BE USED. Refer to
Figure 1.
Units may also be moved or lifted with a forklift, from
the side only, providing that an accessory skid is used.
LENGTH OF FORKS MUST BE A MINIMUM OF 90".
Refer to the Physical Data Table 7 for unit weights and
to the Figures 2 or 12 for approximate center of gravity.
Before lifting a unit, make sure that all panels
are in place and that its weight is distributed
equally on all cables so it will lift evenly.
18
FIGURE 1 - TYPICAL RIGGING
FIGURE 2 - CENTER OF GRAVITY

CLEARANCES

All units require certain clearances for proper operation
and service. Installer must make provisions for ade-
quate combustion and ventilation air in accordance
with Section 5.3, Air for Combustion and Ventilation of
the National Fuel Gas Code, ANSI Z223.1 (in U.S.A.)
or Sections 7.2, 7.3 or 7.4 of Gas Installation Codes
CSA-B149.1 (in Canada) and/or applicable provisions
of the local building codes. Refer to Dimensions and
Clearances Figure 12 for the clearances required for
combustible construction, servicing, and proper unit
operation.
Do not permit overhanging structures or shrubs
to obstruct outdoor air discharge outlet, com-
bustion air inlet or vent outlets.
127915-YIM-A-0405
47.5" (15, 20, 25 TON)
Unitary Products Group