3 Functions of NB-Designer
Addresses
9152~9167
Display Pinyin character input currently
when using Pinyin
9170
Page up/down of Note Book component
9180~9187
Text display of maximum value of
Number Input
9190~9197
Text display of minimum value of Number
Input
9200~9205
Time value of browsing point of Data Log These six words are used to display second, minute,
9210
Display values of each channel during
referencing
9260~9261
Start address for RW clearing operation
9262~9263
Word length of RW clearing operation
9264~9279
Mask code of PLC Station No.(COM 2)
9296~9299
Mask code of error information
9300
Name of path referred by File List
component
9332
Name of file selected by File List
component
9364
Setting Import and Export
9366
Description of processing File Browsing
Component
9370
Confirm Operation method
9380~9395
History value of Number Input
component
9416~9431
Index memory for Station No. variable
9432~9447
memory for indicating communication
state (COM 2)
9465
Time-out ratio of Macro
9470
File name of the screen shot
9486~9501
User name
9502~9503
User password
9504~9505
Current user permission
3-326
Descriptions
NB-series Programmable Terminals NB-Designer Operation Manual(V106)
Comments
(Read)
The value of this LW means the start line of input area.
(Read)
(Read)
hour, day, month and year respectively in BIN code
(read).
The current value of each channel is displayed one by
one according to the bit width of the browsed Data Log
(read).
Sets the start address for RW clearing operation
triggered by LB9130 (read/write).
Sets the word length for RW clearing operation
triggered by LB9130 (read/write).
Each bit corresponds to one Station No. of COM 2 (i.e.
9264.0 corresponds to Station No. 0... and 9279.F
corresponds to Station No. 255). When the bit is turned
ON, the communication corresponding to Station No.
will be stopped (read/write).
Each bit corresponds to one piece of error information.
When the bit is turned ON, the corresponding prompt
error information will not be displayed. Refer to 3-11-4
System Information Table (Page 3-329) in NBDesigner
Operation Manual for details. (read/write).
The name of path currently referred (32 words) by the
File List Component will be specified.
The name of file selected (32 words) by the File List
Component will be specified.
Specify the Import and Export of the project and the
Recipe (read/write).
"1" indicates Copy, "2" does Cut, and "3" does Paste,
respectively (write).
Confirm Operation method: 1: Confirm; 2: Cancel
(write).
Specify the data set before the input operation (read).
Each word corresponds to the index (0~15) for Station
No. variable (read/write).
Each bit corresponds to one Station No. (9432.0
corresponds to 0,
, and 9447.F corresponds to 255).
...
The relevant bit is set to ON when PLC is under time-
out condition and has no response, otherwise it will be
set to OFF (read).
Specify the maximum time allocating to the execution
of a Macro. The time multiplying the default value, 200
ms with the specified value will be the maximum time
(read/write).
The prefix text string of 16 words naming the screen
shot which is stored in USB memory.
Inputs the login user name of up to 32 characters
(read/write).
Inputs the password corresponding to the login user
(read/write).
Displays 32 authorities corresponding to current login
users (read).

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents