PREPARING THE INSTALLATION
Deciding on Where to Install the Air Conditioner (Continued)
MH070FXA4B / MH080FXA4B

Indoor unit
020/023/026/030/035/052
CAUTION:
3 m as minimum pipe length: It will
reduce noise and vibration.
This value must be increased at 7.5
meters in case it is connected just one
indoor unit.
300 mm
minimum
600 mm
minimum
Piping length and the height
Dimension
Composition
System can work with one indoor unit connected, but it is recommended that the TOTAL number
of indoor unit suggested by manufacturer are connected to obtain the maximum performance.
8
E-
08'FJM_OUTDOOR_28896A_IM_E.indd 8
Power supply
Outdoor unit
Ø, V, Hz
MH070FXA4B
1,220-240, 50
MH080FXA4B
200 mm
or more
100 mm
or more
600 mm
minimum
A
300 mm
minimum
1 Room max
4 Room total max
length
length
25m
70 m
A,B,C,D
A+B+C+D
Make at least one round:
It will reduce noise and vibration
The appearance of the unit may be different from the diagram depending on the model.
Piping outside diameter
Unit
Liquid
1/4"
020/023/026/030/035
1/4"
052
160 mm
or more
B
C
Main power switch
Max height between
indoor unit & outdoor unit
15m
(H)
Outside diameter
Gas
3/8"
1/2"
(h)
(H)
D
Max height between
indoor units
7.5 m
(h)
2007-12-12 14:28:11