Samsung MH040FXA2B Installation Manual page 30

Free joint multi & multi-split type room air conditioner
Table of Contents

Advertisement

COMPLETING THE INSTALLATION
Switch Setting and Testing Operation (Cont.)
The designs and shape are subject to
change according to the model.
SW02
Switch
DIS01
Indoor unit
address
K 2
View data display
Outdoor PCB Display
30
E-
08'FJM_OUTDOOR_28896A_IM_E.indd 30
It could take maximum 60 minutes to operate for the protection of the compressor
if the outdoor temperature is below -5°C.
Ampere Limit Setting & Changing Procedure
WARNING
 Do not adjust the "Ampere Limit Switch", if it's not necessary: before modifying
it, evaluate the total number of electric and electronics loads consumption and
use "Ampere limits switch" just as emergency solution or in case the system is
anyway oversized compared to real thermal load needed.
 "Ampere Limit Switch" is initially set to the default value (table below).
 "Ampere Limit Switch" is on the PCB of outdoor unit.
 Contact the authorized service technician or dealer for setting and changing
the "Ampere Limit Switch".
 Before changing the "Ampere Limit Switch", turn off the main power of the system.
MH040FXA2B
MH18VF1X
MH19VF1X
SW01
9.0A
(Default)
K 1
DIS02
8.5A
8.0A
K 3
K 4
7.0A
Ampere
MH070FXA4B
MH050FXA2B MH060FXA3B
MH080FXA4B
13.5A
14.5A
16.6A
(Default)
(Default)
(Default)
11.0A
13.0A
14.0A
9.0A
10.0A
11.0A
8.0A
8.0A
10.0A
Switch Selection
Switch
3
4
ON
ON
(OFF)
ON
OFF
(OFF)
OFF
ON
(OFF)
OFF
OFF
(OFF)
2007-12-12 14:28:54