  • Page 1 INSTALLATION MANUAL MHFNCA Series Free Joint Multi Air Conditioner (Cooling and Heating) DB98-29163A(1)
  • Page 3: Table Of Contents

    Contents  REPARING FOR NSTALLATION Safety Precautions ..........3 ...
  • Page 4: Safety Precautions

    Safety Precautions Keep this installation manual together with the user’s manual in a handy place so that you can find it whenever you need to see it after reading this manual thoroughly.  Make sure to read the following safety precautions carefully before installation. ...
  • Page 5 WARNING  This indicates the possibility of serious injury or death.    The unit should be installed in Check if the voltage and the Do not attempt to repair, accordance with the National frequency of the main power move, modify or reinstall Electrical regulations.
  • Page 6: Choosing The Installation Location

    REPARING FOR NSTALLATION Choosing the Installation Location Indoor Unit Outdoor Unit  Where airflow is not blocked  Where it is not exposed to strong wind  Where cool air can be distributed throughout the room  Well ventilated and dustless places ...
  • Page 7: Accessories

    REPARING FOR NSTALLATION Accessories The following accessories are supplied with the air conditioner:  The number of each accessory is indicated in parentheses. Accessories in the Indoor Unit Case Installation Plate (1) Remote Control (1) Batteries for User’s Manual (1) Installation Manual (1) Remote Control (2) The following connection accessories are optional.
  • Page 8: Nstalling The

    Ø2.56 inch (65mm) bolts must not project more than 0.8inch(20mm). Determine the positions of the wooden uprights to be attached to the window frame. MH026FNCA MH052FNCA MH035FNCA Attach the wooden uprights to the window frame giving attention to the inch inch weight of the indoor unit.
  • Page 9: Installing And Connecting The Assembly Pipe Of The Indoor Unit

    NSTALLING THE IR CONDTIONER Installing and Connecting the Assembly Pipe of the Indoor Unit Connect indoor and outdoor units with field-supplied copper pipes by means of flare connections. Use insulated seamless refrigeration grade pipe only, (Cu DHP type according to ISO1337), degreased and deoxidized, suitable for operating pressures of at least 4200 kPa and for burst pressure of at least 20700 kPa.
  • Page 10: Cutting Or Extending The Pipe

    NSTALLING THE IR CONDTIONER Cutting or Extending the Pipe A 24.6ft pipe is supplied with the air conditioner. (optional) The length of the pipe can be: Extended up to 49.2 ft  Shortened as required  Make sure that you have the required tools (pipe cutter, reamer, flaring tool and pipe holder.) If you want to shorten the pipe, cut it using a pipe cutter, ensuring that the cut edge remains at 90°...
  • Page 11: Installing And Connecting The Drain Hose Of The Indoor Unit

    NSTALLING THE IR CONDTIONER Installing and Connecting the Drain Hose of the Indoor Unit When installing the drain hose for the indoor unit, check if condensation draining is adequate. When passing the drain hose through the2.56 inch hole drilled in the wall, check the following: less Ditch Do NOT place the end...
  • Page 12: Changing Direction Of The Drain Hose

    NSTALLING THE IR CONDTIONER Changing Direction of the Drain Hose You can select the direction of the drain hose, depending on where you want to install the indoor unit. Detach the rubber cap with the flyer. Screw hole Screw Detach the drain hose by pulling it and turning to the left. Drain hose Insert the drain hose by fixing it into the groove of the drain hose and the outlet of the drain pan.
  • Page 13: Connecting The Assembly Cable

    NSTALLING THE IR CONDTIONER Connecting the Assembly Cable When you install the unit, make first refrigerant connections and then elec- trical connections.Connect the air conditioner to grounding system before performing the electrical connection.If unit is uninstalled first disconnect electrical cables, then refrigerant connections. Extend the assembly cable if necessary.
  • Page 14: Assigning Address To Indoor Unit

    NSTALLING THE IR CONDTIONER Assigning Address to Indoor Unit Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan. Open the front grille by pulling on the tabs on the lower right and left sides of the indoor unit.
  • Page 15: Completing The Installation

    OMPLETING THE NSTALLATION Fixing the Indoor Unit in Place After checking for gas leaks in the system, insulate the pipe, hose and cables. Then place the indoor unit on the installation plate. To avoid condensation problems, place heat-resistant polyethylene foam separately around each refrigerant pipe in the lower part of the indoor unit.
  • Page 16: Final Check And Trial Operation

    OMPLETING THE NSTALLATION Final Check and Trial Operation To complete the installation, perform the following checks and tests to ensure that the air conditioner operates correctly. Check the following: Strength of the installation site  Tightness of pipe connection to detect gas leak ...
  • Page 17: Providing Information For User

    Providing Information for User After finishing the installation of the air conditioner, explain the following to the user: (refer to appropriate pages in the User’s Manual.) How to start and stop the air conditioner How to select the modes and functions How to adjust the temperature and fan speed How to adjust the airflow direction How to set the timers...