PREPARING THE INSTALLATION
Deciding on Where to Install the Air Conditioner (Continued)
MH050FXA2B

Indoor unit
020/023/026/035/052
MH052FX
-MH052FMEA/MH052FUEA
CAUTION:
3 m as minimum pipe length: It will reduce
noise and vibration.
This value must be increased at 7.5 meters
in case it is connected just one indoor unit.
300 mm
minimum
600 mm
minimum
Piping length and the height
Dimension
Composition
System can work with one indoor unit connected, but it is recommended that the TOTAL number
of indoor unit suggested by manufacturer are connected to obtain the maximum performance.
6
E-
08'FJM_OUTDOOR_28896A_IM_E.indd 6
Power supply
Outdoor unit
MH050FX
A2B
1,220-240, 50
A2B outdoor unit cannot be connected to the following indoor unit combination.
200 mm
or more
100 mm
or more
600 mm
minimum
300 mm
minimum
1 Room max
2 Room total max
length
length
20m
30 m
A,B
A+B
Make at least one round:
It will reduce noise and vibration
The appearance of the unit may be different from the diagram depending on the model.
Piping outside diameter
Unit
Ø, V, Hz
020/023/026/035
052
160 mm
or more
A
Main power switch
Max height between
Max height between
indoor unit & outdoor unit
15m
(H)
Outside diameter
Liquid
Gas
3/8"
1/4"
1/2"
(h)
(H)
B
indoor units
7.5 m
(h)
2007-12-12 14:28:03