Note 1:
The heating capacity of the PRESTIGE
SOLO 110 is based on the test requirements
of the U.S. Department of Energy.
Note 2:
The IBR rating is based on a piping and pick
up allowance of 1.15. This allowance should
be sufficient for the standard radiation
requirements for a building load.
16.0
14.0
12.0
10.0
8.0
6.0
4.0
2.0
0.0
4.0
5.0
Graph 1: Pressure Loss Through Boiler
Note: Minimum allowable flow rate at full input:
Natural - 3.9 gpm
Propane - 3.5 gpm
Note 3:
Note 4:
Pressure Drop Comparison
6.0
7.0
8.0
Flow Rate (GPM)
62
Based on the given AFUE the PRESTIGE
SOLO 110 meets the energy eff i c i e n c y
guidelines established by Energy Star.
Input and output ratings are shown for sea
level applications. The PRESTIGE SOLO
automatically derates the input at approxi-
mately 2% for every 1,000 Ft. of altitude. No
alterations to the boiler or burner system is
required.
Solo 110
Taco 007
Grundfos UPS15-58F/FC - Spd 3
9.0
10.0
11.0
12.0