3100 Series ACC Wood Burner

FLOOR PROTECTOR

Quadra-fire 3100 Millenium ACC does not require a insulating Floor Protector, as they are tested and
comply with the minimum Floor Protector requirements of AS/NZS 2918:2001.
Note:
▪ The minimum Floor Protector sizes are specified in the clearance chart, see Table 1 & 2.
▪ A Floor Protector can include ceramic tiles with grouted joints fixed directly onto a wooden floor or
a sheet of toughened glass, panel steel or any other non combustible material laid directly onto a
wooden floor.
▪ If installed directly onto a concrete slab, the concrete slab can be considered as the floor
protector,but must maintain the minimum measurement listed.
PARALLEL POSITIONNG
Fig. 3
REAR WALL
G
F
FLOOR PROTECTOR
Table 1
A
Min. Clearance from back of unit to rear wall
B
Min. clearance from center of spigot to rear wall
C
Min. distance from front of base to floor protector front
D
Min. floor protector front width
E
Min. distance from rear wall to front of floor protector
F
Min. distance from unit side to side wall
G
Min. clearance from center of spigot to side wall
NOTE: HEAT SHIELD REQUIREMENTS FOR HEAT SENSITIVE WALLS
Clearances may be reduced by provision of an appropriately located heat shield refer to
AS/NZS 2198:2001 3.2.3 TABLE 3.1
Page 4
E
D
DESCRIPTION
Pioneer Double Flue Mounted Shield Universal
Shall be Fitted
7033-308B
B
C
With Double Flue
Shield Fitted
175
345
300
800
1062
360
668
January 17, 2013
R
A