Supplying Make Up Air; Water Line Hookup; Low Water Temperature Protection - Pro-Fab Industries 100 Installation And Operation Instructions Manual

Hot water furnace
Table of Contents

Advertisement

Supplying Make Up Air

Fireplaces, other furnaces, clothes dryers, exhaust fans,
and other appliances all draw air from the room in which
they are located. The Empyre Elite adds to that draw, mak-
ing it important to ensure there is an adequate source of
fresh air to offset these demands. Otherwise, a negative
pressure may be created in the room and starve combus-
tion in the furnace.
1. Determine the volume of space (cubic feet) in the
room. Include in the calculation adjacent rooms and
areas not closed off by doors.
Volume (CF) = Length (ft) x Width (ft) x Height (ft)
2. Determine the air input requirements of all applianc-
es in the space. Add them and round the total to the
nearest 1000 BTU per hour. The Empyre Elite 100 re-
quires 85 CFM (cubic feet/minute), the Elite 200 re-
quires 120 CFM.
3. Determine whether the space is 'confined' or 'uncon-
fined' by dividing the total volume of the room by the
total input requirements for all appliances in the room.
a. If the result is equal to or greater than 50 CF/1000
BTU per hour, then consider the space 'unconfined.'
b. If the result is less than 50 CF/1000 BTU per hour,
then consider the space 'confined.'
4. For an 'unconfined' space in a conventionally con-
structed building, the fresh air infiltration through
cracks around windows and doors NORMALLY pro-
vides adequate air for combustion and ventilation,
and therefore no additional make up air is required.
5. For a 'confined' space or an 'unconfined' space in a
building with unusually tight construction, an addition-
al source of make up air is required. Please consult an
HVAC professional to determine the best way to supply
make up air for this type of installation.
Important: Furnace room must never be in a negative
pressure condition. Negative pressure could result in
smoke in the room.

Water Line Hookup

It is recommended that a line be installed between the
overflow port and suitable catch pan or drain.
1. Hook up supply to "Supply" port and return to "Return"
port as indicated (see page 8).
2. Install shut off valves on all lines attached to the fur-
nace to prevent loss of water during maintenance and
repairs.
EMPYRE ELITE INSTALLATION AND OPERATION MANUAL • 2011

Low Water Temperature Protection

IT IS THE RESPONSIBILITY OF THE INSTALLER TO
PROVIDE LOW WATER TEMPERATURE PROTECTION
IN THE DESIGN OF THE HEAT DISTRIBUTION SYSTEM
The Empyre Elite furnace is no different than an oil boil-
er or gas boiler in that condensation of the products of
combustion will occur if flue gases come in contact with
a surface that is less than 140°F (60°C). With an oil or
gas boiler the rate of fuel and consistency of the fuel is
automatic, so if the temperature of the water in the boiler
falls below the desired setting the burner comes on auto-
matically raising the water temperature. The Empyre Elite
requires an automatic protection from low water tempera-
ture because of the manual fuel feed.
Condensation (water) in the boiler tubes will cause corro-
sion and premature failure. There are many ways of pre-
venting the temperature from falling too low.
See Figures 1 through 6 for sketches of low water tem-
perature protection options.
Figure 1 - Return Water Temperature Control
- connecting to a closed system
- using an aquastat to control pump on secondary loop
Figure 2 - Return Water Temperature Control
- using aquastat to control pump on secondary loop
- 2 pumps required
- shown on a primary / secondary loop
- primary pump to be ON at all times.
INSTALLATION
11

Advertisement

Table of Contents
loading

This manual is also suitable for:

200Empyre elite 100Empyre elite 200

Table of Contents