Wired Remote Controller; Simple Remote Controller - Fujitsu R407C Service Manual

Multi air conditioning system for buildings
Table of Contents

Advertisement

5-3 REMOTE CONTROLLER

5-3-1 WIRED REMOTE CONTROLLER

NON STOP
TIMER
MODE
CLOCK ADJUST
If there is a problem with the air conditioner, it will
stop running and " EE:EE " will be displayed instead
of the clock.
(1) If the operation lamp is on then press START/
STOP button to turn it off.
(2) Press the SET TIMER button ( ) and SET
TEMP./DAY button ( ) at the same time for more
than three seconds to start the self diagnosis check.
An error code will be displayed in the clock display area.
(3) Press the SET TIMER button ( ) and SET
TEMP./DAY button ( ) again for more than three
seconds to end the self diagnosis check.
Error code history can be displayed when UTB- LB type
wired remote controllers is used.Please refer to
"Installation Instruction Sheet" of the controller.

5-3-2 SIMPLE REMOTE CONTROLLER

If there is a problem with the air conditioner it will stop
running and " EE:EE " will be displayed.
(1) If the operation lamp is on then press
button to turn it off.
(2) Press the
and the
for more than three seconds to start the self diagnosis
check.
An error code will be displayed display area.
(3) Press the
and the
three seconds to end the self diagnosis check.
Error code history can be displayed. Please refer to
"Installation Instruction Sheet" of the remote controller.
CLOCK
COOL
C
SET TIME
TEMP./DAY
FAN
CONTROL
MASTER
CONTROL
ZONE
ENERGY SAVE
START/STOP
SET
DAY OFF
Error Code
Remote controller
address
SET
buttons at the same time
buttons again for more than
TIMER
SET TIME
TEMP./DAY
MODE
CONTROL
CLOCK ADJUST
ZONE
ENERGY SAVE
SET
SET
Error code displayed on wired or simple remote controller
Error Code
05-05
Error Code
FAN
Remote controller
MASTER
CONTROL
address
START/STOP
DAY OFF
Error contents
No error
Model information abnormal
Power supply frequency abnormal
EEPROM access error
EEPROM deletion error
Room temperature themistor error
Indoor unit heat exchanger themistor
(middle) error
Indoor unit heat exchanger themistor
(inlet) error
Indoor unit heat exchanger themistor
(outlet) error
Blower temperature themistor error
Drain abnormal
Room temperature abnormal
Indoor unit fan error
Transmission error
Node setting error
Parallel communication error
Outdoor unit error

Hide quick links: