Laars Pennant PNCH Installation And Operation Instructions Manual page 39

Hydronic boiler and water heater
Table of Contents

Advertisement

Pennant
( 500-2000 )
time selected after the heat demand in the system is
satisfied. This setting also affects the 24VAC output
on the "PMP" "PMP" terminals (see Section 5.2).
These terminals can power a contactor for a larger
system pump. Laars recommends a minimum pump
delay setting of 5 minutes. See Section 6.4.6 for more
information.
NOTE: In modes other than mode 6, the pump will run
continuously if the "HtD" and "ComD" terminals are
jumpered and not connected to a zone valve or pump
end switch, or other "contact closure" device to indicate
when the heat demand in the system is satisfied. The
pump will never run, and the boiler will never fire, if the
jumper is removed and the terminals left empty.
OUTDOOR RESET
OUTDOOR RESET
OUTDOOR RESET (modes 4 and 5): Outdoor reset
OUTDOOR RESET
OUTDOOR RESET
adjusts the target temperature based on the outdoor air
temperature and reset ratio. The reset ratio is
determined from the Boiler Start, Boiler Design,
Outdoor Start and Outdoor Design settings.
HEAT DEMAND
HEAT DEMAND
HEAT DEMAND – For heat demand to exist, there
HEAT DEMAND
HEAT DEMAND
must be continuity between the Com D (common
demand) and Ht D (heat demand) terminals. The
Pennant ships with a jumper between these terminals.
The control also evaluates the sensor(s) installed
in the system. If the control is not in warm weather
shutdown (WWSD), and the sensor(s) are below the
target temperature, the "Dem" segment is turned on in
the display. The control energizes the pump (on pump
mounted boilers) and energizes both "PMP" terminals.
The pump symbol appears in the display (see Figures
25 and 26). The control then operates the stages to
maintain the setpoint temperature.
Boil Start (Boiler Start): The BOIL START
Boil Start
Boil Start
Boil Start
Boil Start
temperature is the theoretical boiler supply
temperature that the heating system requires when the
Figure 26. Temperature Control Symbol Description.
outdoor air temperature equals the OUTDR START
temperature setting.
EXAMPLE 1
DHW (Mode 3) Programming. For domestic
hot water systems up to 175°F / 79°C, use mode 3 as
described below.
Step 1: Install the additional sensor into the
storage tank, wiring it to "SC2" and "SUPS" terminals
on the field wiring panel (Figure 23).
Step 2: Press the three programming buttons to
enter ADJUST
ADJUST
ADJUST
ADJUST
ADJUST mode (Figure 25). Press ITEM
the programming item, and the arrow keys to adjust the
TARGET TANK
TARGET TANK
setting. TARGET TANK
TARGET TANK
TARGET TANK is desired tank temperature.
Recommended settings with a desired tank temperature
of 125°F:
Example DHW Programming
Item
MODE
BOIL TARGET
TARGET TANK
DIFF TANK
BOIL MASS
DIFF
DLY
Step 4: See Section 6.4.11 Limit Controls. Set
both high limits 25°F / 14°C higher than BOIL TARGET
to allow for temperature rise across heat exchanger.
Manual high limits on water heaters have a maximum
200°F / 93°C setting. (If water must be at 175°F /
79°C or higher with a volume water heater model, use
mode 1. For volume water applications exceeding
200°F / 93°C, contact the factory.)
Fine tuning: For faster staging, increase BOIL
TARGET
TARGET
DIFF TANK
DIFF TANK
TARGET setting. Larger DIFF TANK
TARGET
TARGET
DIFF TANK
DIFF TANK and DIFF
will slow response to demand, but may save energy.
If unit short cycles, enter Advanced Programming
mode (Section 6.4) and increase BOILER MAX
the BOIL TARGET
BOIL TARGET
BOIL TARGET
BOIL TARGET setting or higher. Set BOILER MIN
BOIL TARGET
STGMODE
STGMODE
120°F / 49°C, and STGMODE
STGMODE to PID
STGMODE
Advanced Programming Mode to enter Advanced
Programming mode, or contact the factory for
assistance.
Figure 27. Temperature Control Target Temperature
Graph.
Page 39
ITEM
ITEM
ITEM to select
ITEM
3
3
140°F
60°C
125°F
52°C
2°F
1°C
1
1
2°F
1°C
5:00
5:00
°C
BOIL TARGET
BOIL TARGET
BOIL TARGET
BOIL TARGET
BOIL
BOIL
BOIL
BOIL
DIFF
DIFF
DIFF
DIFF settings
BOILER MAX
BOILER MAX
BOILER MAX
BOILER MAX setting to
BOILER MIN to
BOILER MIN
BOILER MIN
BOILER MIN
PID
PID
PID
PID. See Section 6.4.12

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents