Laars Pennant PNCH Installation And Operation Instructions Manual page 17

Hydronic boiler and water heater
Table of Contents

Advertisement

Pennant
( 500-2000 )
C
130°F
CAUTION: THIS DRAWING SHOWS SUGGESTED
PIPING CONFIGURATION AND VALVING, CHECK
WITH LOCAL CODES AND ORDINANCES FOR
ADDITIONAL REQUIREMENTS.
LEGEND
THERMOMETER
PURGE
TEMPERATURE
VALVE
SENSOR
GLOBE VALVE
CHECK VALVE
PRESSURE REDUCING VALVE
W/ FAST FILL BYPASS
Figure 6. Hydronic Piping — One Boiler, Multi-Temperature System.
150°F
PUMP LOCATION FOR
NON-PUMP-MOUNTED UNITS
PUMP LOCATION FOR PUMP-MOUNTED UNITS
EXPANSION TANK
WITH AIR SCOOP AND
AUTO AIR VENT
3-WAY VALVE
VALVE
PUMP
C
COLD WATER
MAKE-UP
180°F
C
SYSTEM PUMP
NOTES:
1. BOILER LOOP IN EXAMPLE IS MAINTAINED AT 180°F.
2. ZONE THERMOSTATS CAN BE INTERLOCKED WITH BOILER,
SO THAT BOILER FIRES UPON CALL FOR HEAT FROM ANY
ZONE.
3. ZONE PIPING AND INTERLOCK WIRING TO BE DESIGNED
BY SYSTEM ENGINEER.
PRIMARY/SECONDARY MANDITORY FOR ALL
VARIABLE FLOW SYSTEMS
INSTALL AIR VENTS AT HIGH POINTS IN SYSTEM
PIPING & SIZING OF EXPANSION TANK
PER TANK MANUFACTURER'S INSTRUCTIONS
DIMENSION "C" (COMMON PIPING) TO BE FOUR
PIPE DIAMETERS, MAX. (NO ELBOWS OR VALVES)
BOILER CIRCUIT PIPING MUST BE EQUAL
TO BOILER WATER CONNECTION SIZE
BOILER CIRC. PUMP SIZED FOR FLOW THROUGH BOILER
DOTTED DEVICES INDICATE ALTERNATE LOCATIONS
PUT BOILER CONTROL SENSOR IN THE SYSTEM
SUPPLY WHEN USING THIS PIPING STYLE.
MINIMUM BOILER INLET WATER TEMPERATURE
MUST BE AT LEAST 120°F.
Page 17