Electrical specifications
Model EWWP
Power supply
• Phase
• Frequency
(Hz)
• Voltage
(V)
• Voltage tolerance
(%)
• Recommended fuses
(aM)
Compressor
• Phase
• Frequency
(Hz)
• Voltage
(V)
• Nominal running current
)
(A
Control
• Phase
• Frequency
(Hz)
• Voltage
(V)
• Recommended fuses
(aM)
D
ESCRIPTION
The EWWP packaged water-cooled water chillers are available in 7 standard sizes with nominal cooling capacities ranging from 13 to 65 kW.
14
15
EWWP014~035KB
1
4
9
19
11
Figure - Main components
1
Compressor
2
Evaporator
3
Condenser
4
Switchbox
5
Chilled water in
6
Chilled water out
7
Condenser water out
8
Condenser water in
9
Evaporator entering water temperature sensor
10
Freeze up sensor
(1) Refer to the engineering data book for the complete list of specifications.
EWWP014~065KBW1N
Packaged water-cooled water chillers
4PW61660-1A – 04.2012
(1)
014
022
028
3N~
50
400
±10
3x 16
3x 20
3x 25
3~
50
400
6.6
10.4
13.1
1~
50
230
factory installed
16
17
2
3
12
7
5
13
8
6
035
Model EWWP
Power supply
• Phase
• Frequency
• Voltage
• Voltage tolerance
3x 32
• Recommended fuses
Compressor
• Phase
• Frequency
• Voltage
15.0
• Nominal running current
Control
• Phase
• Frequency
• Voltage
• Recommended fuses
EWWP045~065KB
18
2
3
1
1
4
500
10
11
11
Condenser entering water temperature sensor
12
Digital display controller
13
Power supply intake
14
Ball valve (field installed)
15
Water filter (field installed)
16
Air purge valve (field installed)
17
T-joint for air purge (field installed)
18
Flow switch (with T-joint) (field installed)
19
Main switch
Required space around the unit for service
045
055
3N~
50
(Hz)
400
(V)
±10
(%)
3x 40
3x 50
(aM)
3~
50
(Hz)
400
(V)
10.4
13.1
(A)
1~
50
(Hz)
230
(V)
factory installed
(aM)
9
12
5
19
14
6
10
065
3x 50
15.0
500
7