EWWD120MBYNN EWWD280MBYNN EWWD500MBYNN
EWWD180MBYNN EWWD360MBYNN EWWD520MBYNN
EWWD240MBYNN EWWD440MBYNN EWWD540MBYNN
C
ONTENTS
Introduction ....................................................................................... 1
Options and features ................................................................................. 1
Operation range ................................................................................ 2
Main components.............................................................................. 2
Piping insulation ................................................................................ 5
Field wiring ........................................................................................ 5
Parts table.................................................................................................. 5
Before starting................................................................................... 7
How to continue................................................................................. 8
Thank you for purchasing this Daikin air conditioner.
READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN YOUR
FILES FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF EQUIP-
MENT OR ACCESSORIES COULD RESULT IN ELECTRIC
SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAM-
AGE TO THE EQUIPMENT. BE SURE ONLY TO USE
ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFI-
CALLY DESIGNED FOR USE WITH THE EQUIPMENT AND
HAVE THEM INSTALLED BY A PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE
AND INFORMATION.
I
NTRODUCTION
The Daikin EWWD-MBYNN packaged water-cooled water chillers
are designed for indoor installation and used for cooling applications
only. The units are available in 9 standard sizes with nominal cooling
capacities ranging from 120 to 540 kW.
The EWWD units can be combined with Daikin fan coil units or air
handling units for air conditioning purposes. They can also be used
for supplying chilled water for process cooling.
The present installation manual describes the procedures for unpack-
ing, installing and connecting the EWWD units.
Installation manual
1
Packaged water-cooled water chillers
Technical specifications
Page
Model EWWD
Dimensions HxWxD
Weight
• machine weight
• operation weight
Connections
(1)
• chilled water inlet/outlet
• condenser water inlet/outlet
Model EWWD
Dimensions HxWxD
Weight
• machine weight
• operation weight
Connections
(1)
• chilled water inlet/outlet
• condenser water inlet/outlet
Model EWWD
Dimensions HxWxD
Weight
• machine weight
• operation weight
Connections
(1)
• chilled water inlet/outlet
• condenser water inlet/outlet
®
(1) Victaulic
coupling
Electrical specifications
Model EWWD
Power circuit
• Phase
• Frequency
• Voltage
• Voltage tolerance
Options and features
Options
Suction stop valve
Ampere and voltmeter
Main isolator switch
Dual pressure relief valve on the condenser
Low noise operation
BMS-Connection (MODBUS/J-BUS, BACNET, LON)
Features
Glycol application for leaving evaporator water down to -10°C
Daikin Integrated Chiller Network (DICN)
Liquid line solenoid valve
Sight glass with moisture indication
Voltage free contacts
•
general operation/pumpcontact
•
alarm
•
operation circuit 1
•
operation circuit 2 (only for EWWD360~540)
(1) Refer to the operation manual or engineering data book for the complete
list of specifications, options and features.
Installation manual
(1)
120
180
(mm)
1014x2672x930
(kg)
1000
1273
(kg)
1032
1318
3" OD
3" (88.9 mm OD)
(inch)
(76 mm OD)
(1)
2-1/2"
3" (88.9 mm OD)
(inch)
280
360
(mm)
1014x2672
2000x2672x930
x930
(kg)
1613
2546
(kg)
1693
2636
3" (88.9 mm OD)
(inch)
(1)
3" (88.9 mm OD)
(inch)
500
520
(mm)
2000x2672x898
(kg)
3034
3150
(kg)
3156
3281
3" (88.9 mm OD)
(inch)
(1)
3" (88.9 mm OD)
(inch)
(1)
120~540
3~
(Hz)
50
(V)
400
(%)
±10
(1)
EWWD120~540MBYNN
Packaged water-cooled water chillers
240
1527
1588
440
2800
2902
540
3346
3485