Check Manual Air Vents; Test Low Water Cutoff (If Installed); Reset Button (Low Water Cutoff); Check Boiler Piping (Gas And Water) - Lochinvar 40 - 120 User's Information Manual

Heating boiler
Table of Contents

Advertisement

2
Maintenance schedule
Check air vents
1.
Reference FIG. 2-3 below.
2.
Visually inspect vent to make sure that no leaks are
present.
3.
If there is leaking, turn the valve all the way to the right,
to the valve closed position (FIG. 2-3).
If the leak continues, contact a qualified heating installer
4.
or service technician.
Figure 2-3 Manual Air Vent
SECURE HOSE BEFORE
OPENING VALVE
CLEAR HOSE RATED
FOR MINIMUM 120° F
VALVE OPENED
VALVE CLOSED

Test low water cutoff (if installed)

1.
If the system is equipped with a low water cutoff,
test the low water cutoff periodically during the heating
season, following the low water cutoff manufacturer's
instructions.

Reset button (low water cutoff)

1.
Testing the low water cutoff shuts the unit off. Press the
RESET button on the low water cutoff to turn the unit
back on.

Check boiler piping (gas and water)

1.
Remove the boiler front access door and perform a gas
leak inspection per steps 1 through 7 of the Operating
Instructions on page 9. If gas odor or leak is detected,
immediately shut down the boiler following the procedures
on page 9. Call a qualified service technician.
2.
Visually inspect for leaks around water piping.
Also inspect the circulators, relief valve, and fittings.
Immediately call a qualified service technician to repair
any leaks.
Have leaks fixed at once by a qualified
WARNING
service technician. Failure to comply could
result in severe personal injury, death, or
substantial property damage.
3.
Replace the front access door.
8

Operate relief valve

1.
Before proceeding, verify that the relief valve outlet has
been piped to a safe place of discharge, avoiding any
possibility of scalding from hot water.
WARNING
2.
Read the boiler pressure/temperature gauge to make
sure the system is pressurized.
top lever slightly, allowing water to relieve through
the valve and discharge piping.
IMG00272
3.
If water flows freely, release the lever and allow the valve
to seat. Watch the end of the relief valve discharge pipe
to ensure that the valve does not weep after the line has
had time to drain. If the valve weeps, lift the seat again to
attempt to clean the valve seat. If the valve continues to
weep afterwards, contact your qualified service
technician to inspect the valve and system.
4.
If water does not flow from the valve when you lift the
lever completely, the valve or discharge line may be
blocked. Immediately shut down the boiler, following
the operating instructions on page 9 of this
manual. Call your qualified service technician to inspect
the boiler and system.
Shut boiler down (unless boiler is used
for Domestic Water)
1.
Follow "To Turn Off Gas to Appliance" on page 9
of this manual.
2.
Do not drain the system unless exposure to freezing
temperatures will occur.
3.
Do not drain the system if it is filled with an antifreeze
solution.
4.
DO NOT shut down boilers used for domestic water
heating, they must operate year-round.
User's Information Manual
To avoid water damage or scalding due
to valve operation, a metal discharge
line must be connected to the relief
valve outlet and run to a safe place of
disposal.
This discharge line must be
installed by a qualified heating installer
or service technician in accordance with
the instructions in the Cadet Heating
Boiler Installation and Service Manual.
The discharge line must be terminated
so as to eliminate possibility of severe
burns or property damage should the valve
discharge.
Lift the relief valve

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cadet 40Cadet 120

Table of Contents