4
Operating information
Viewable and changeable control parameters
Before changing parameters, note the
CAUTION
settings so that the unit can be returned to
its original operating parameters.
Temperature Units (°C/°F)
The control can be configured to display temperature in
either °C or °F. This parameter can be changed by accessing
parameter u01.
Set SH Temperature
The Space Heat Demand Temperature can be adjusted UP or
DOWN by accessing parameter u02. Temperature range is
32°F to parameter P90.
Set tank DHW Tank Setpoint (if tank sensor present)
The DHW Setpoint Temperature can be adjusted UP or
DOWN by accessing parameter u03. Temperature range is
60°F to 185°F.
Set SH Setpoint at Minimum Outdoor Temperature
When the outdoor air temperature drops to 25°F, the
calculated set point will be at this setting (reference Table 4-3
in the Cadet Heating Boiler Installation and Service Manual).
If the outdoor air temperature drops further, the set point
will continue to increase above this setting. However, if SH
set point is set lower than the calculated set point, the water
temperature will be limited by the SH set point instead. This
parameter can be changed by the installer by accessing the
P01. Temperature range is 68°F to 250°F.
12
User's Information Manual
Access modes
User
Press the ENTER button for 5 seconds.
Installer
Most parameters are available only to the installer, accessible
by entering the installer key combination: Press the ENTER
and DOWN buttons simultaneously for 5 seconds.
Saving parameters
in the Cadet Heating Boiler Installation and Service Manual)
To save parameters and exit programming:
Press the ENTER button to go to the end of the Parameter
List, then press ENTER again. Otherwise, the parameters
will be saved automatically after Timeout.
To enter a parameter and continue programming:
Press the UP or DOWN button to change parameters. Press
ENTER to move to the next parameter and to the end of
the Parameter List. Press ENTER to save and return to
the Base Screen. Otherwise, the parameters will be saved
automatically after Timeout.
(reference the Parameter Table