AH5 00 Hardw are Manu al
The description of the terminals
Terminal
1.
2.
High-speed count:
X0.0+, X0.0-,
X0.1+, X0.1-,
X0.2+, X0.2-,
X0.3+, and
X0.3-
High-speed comparison and
Interrupt inputs
1.
2.
Motion control: The terminals are
High-speed count:
X0.8+, X0.8-,
X0.9+, and
X0.9-
High-speed comparison and
Interrupt inputs
Description
They are differential inputs.
The functions of the terminals:
The terminals are the RESET
inputs for counter 0~counter
5.
X0.0+ and X0.0- are for
counter 0. X0.1+ and X0.1-
are for counter 1. X0.2+ and
X0.2- are for counter 2 and
counter 4. X0.3+ and X0.3-
are for counter 3 and counter
5.
catch: The terminals can function
as trigger signals for a high-speed
catch.
They are differential inputs.
The functions of the terminals:
for a manual pulse generator.
The terminals are for counter
0.
X0.8+ and X0.8- are A-phase
inputs for counter 0. X0.9+
and X0.9- are B-phase inputs
for counter 0.
catch: The terminals can function
as trigger signals for a high-speed
catch.
Maximum input
Response
characteristic
Current
200 kHz
15 mA
200 kHz
15 mA
Voltage
5~24 V
5~24 V
3 - 5 7