Heating Capacity Tables - Daikin FWF-BT Technical Data Manual

Fan coil units 4-way blow ceiling mounted cassette
Table of Contents

Advertisement

6
Capacity tables

6 - 2 Heating Capacity Tables

FWF-BT
Air temperature (°CDB )
Water temperature (Entering °C)
Model
Airfl ow
FWF02BT
FWF03BT
FWF04BT
FWF05BT
Air temperature (°CDB )
Water temperature (Entering °C)
Airfl ow
Model
FWF02BT
FWF03BT
FWF04BT
FWF05BT
NOTE
1.
The water fl ow is the same as for cooling mode in the nominal point. Delta T is not fi xed.
• Indoor Unit • 4-way blow ceiling mounted cassette • FWF-BT
Heating capacity (kW)
HH
2.9
H
2.6
L
2.3
HH
4.0
H
3.4
L
2.8
HH
5.4
H
4.1
L
2.8
HH
6.7
H
5.3
L
3.6
Heating capacity (kW)
HH
2.7
H
2.4
L
2.1
HH
3.7
H
3.1
L
2.6
HH
5.0
H
3.8
L
2.6
HH
6.2
H
4.9
L
3.3
• Fan coil • Indoor Unit
20
50-45
Water fl ow (l/min)
Water pressure drop (kPa)
6.0
6
4.9
4
4.3
4
9.4
19
8.0
14
7.2
12
12.4
31
9.5
19
7.2
12
14.7
42
11.5
27
8.3
15
22
50-45
Water fl ow (l/min)
Water pressure drop (kPa)
6.0
6
4.9
4
4.3
4
9.4
19
8.0
14
7.2
12
12.4
31
9.5
19
7.2
12
14.7
42
11.5
27
8.3
15
1
6
3TW33042-1
11