4.5 Alarm codes

Using a sophisticated self-diagnosis system, the UPS is able to check its own status and any anomalies and/or faults
which may occur during normal operation and display them on the display panel. If there is a problem, the UPS signals
the event by showing the code and the type of active alarm on the display.
A
LARMS
Minor" problems which reduce performance or prevent certain functions from being used.
"
CODE
A007
A107
A10A
A806
A80E
A810
A60D
A802
F
AULTS
Faults are normally preceded by an alarm signal and their scale leads to the power-off of the inverter and the load being
powered by the bypass line.
CODE
F002
F004
F302 F303
F300 F301
F304
F305
F70D
F805
F704
F70C
F808
F811
DESCRIPTION
Fans blocked
Cable connection error
Unbalanced input voltages (three-phase input)
E.P.O control active
Overload: load > 105%
Load percentage greater than the user threshold set
Batteries missing or Battery Box missing or not connected
Low battery
DESCRIPTION
UPS Fault
Dissipator over temperature
Capacitor bank undervoltage
Capacitor bank overvoltage
Unbalanced capacitor bank
Failed capacitor bank soft start
Inverter overvoltage
Short circuit
Failed inverter soft start
Inverter undervoltage
Output overload fault
Negative output power
Page 21