Hitachi SJ700B SERIES Quick Reference Manual page 21

Inverter
Hide thumbs Also See for SJ700B SERIES:
Table of Contents

Advertisement

Symbol
Terminal name
To switch the control logic between sink logic and source logic, change the
jumper connection of this (PLC) terminal to another terminal on the control
circuit terminal block.
Intelligent input
PLC
Jumper terminals P24 and PLC for the sink logic; jumper terminals CM1
(common)
and PLC for the sink logic.
To use an external power supply to drive the contact inputs, remove the
jumper, and connect the PLC terminal to the external interface circuit.
Select five of a total 51 functions, and assign these five functions to
11
terminals 11 to 15.
12
If you have selected an alarm code using the function "C062", terminals 11
13
Intelligent output
to 13 or 11 to 14 are used exclusively for the output of cause code for alarm
14
(e.g., inverter trip). The control logic between each of these terminals and
15
the CM2 terminal always follows the sink or source logic.
Intelligent output
This terminal serves as the common terminal for intelligent output terminals
CM2
(common)
[11] to [15].
Select functions from the 43 available, and assign the selected functions to
these terminals, which serve as C contact output terminals.
AL0
Intelligent relay
AL1
output
AL2
In the initial setting, these terminals output an alarm indicating that the
inverter protection function has operated to stop inverter output.
Connect to an external thermistor to make the inverter trip if an abnormal
temperature is detected.
The CM1 terminal serves as the common terminal for this terminal.
External
[Recommended thermistor properties]
TH
thermistor input
Allowable rated power: 100 mW or more
Impedance at temperature error: 3kΩ
The impedance to detect temperature errors can be adjusted within the
range 0Ω to 9,999Ω.
Chapter 2 Installation and Wiring
Description
2 - 9
Electric property
Voltage drop between each
terminal and CM2 when
output signal is on: 4 V or
less
Maximum allowable
voltage: 27 VDC
Maximum allowable
current: 50 mA
(Maximum contact
capacity)
AL1-AL0: 250 VAC, 2 A
(resistance) or 0.2 A
(inductive load)
AL2-AL0: 250 VAC, 1 A
(resistance) or 0.2 A
(inductive load)
(Minimum contact capacity)
100 VAC, 10 mA
5 VDC, 100 mA
Allowable range of input
voltages
0 to 8 VDC
[Input circuit]
DC8V
10kΩ
TH
1kΩ
Thermistor
CM1