A. PROGRAMMING THE INTELLISWITCH™
To reduce the risk of injury and ensure proper operation all
Notes and instructions shall be read!
Note: The STOP button
STOP
mediately stops the unit for an emergency situation. The
Intelliswitch® will display STBY for Stand By when selected.
To release the control from STBY press STOP again. When
the control is released from STOP it will be in the OFF Mode.
Press the left or right arrows to select new Mode or OK to
return to the clock.
Note: When changing options, if there is no activity for 15
seconds, the control will save changes and default back to
the User Menu display clock.
Note: The OK button
always saves the current entered
value and returns you to the User Menu display clock.
Section 1: Quick Start Reference
Section 2: Arrow Navigation
Section 3: Menu Structure
Section 4: User Menu
Section 5: Program Menu
Section 6: Diagnostic Menu
Section 7: Factory Menu
Section 8: External Connections
1. Quick Start Reference
1.1. Press the Menu button (down Arrow).
1.2. Using the left and right arrows, select the operating
Mode: Off, On, Auto, Deluxe, Comfort Plus or Program
Number 1, 2 or 3.
1.3. Press OK.
2. Arrow Navigation
The up and down arrows
The left and right arrows
level menu options (Mode, Speed, Temp Degree, Temp Set,
T-stat Mode and Day) or are used to enter into multi-level
menu options (Delay Time, Temp Set, Start Time, Stop Time
and Set Time).
Arrow sequence and available settings are illustrated under
each option.
2.1. Single Level Options
Single level options can change values directly with the left and
right arrows. No additional actions are necessary to access these
option settings.
is available at all times and im-
select the menu options.
change values for single-
2.2. Multi-level Options
Multi-level options require additional actions to access an op-
tions setting. The right or left arrow is required to enter into an
option.
If the multi-level option has one value to edit it may be
changed directly with the up and down arrows.
If the multi-level menu option has two values (such as a time
value) the first option value flashes upon selection. Use the left
or right arrow to select which value to change and then use the
up and down arrows to change the option value. See the Menu
Options section for the option increment i.e. hours/minutes,
minutes/seconds.
To leave a multi-level option, use the left or right arrow to cycle
through the option value until it stops flashing. The up or down
arrow may now be used to navigate to the other options.
3. Menu Structure
The Intelliswitch™ has four menus:
User Menu (Section 4)
Program Menu (Section 5)
Diagnostic Menu (Section 6)
Factory Menu (Section 7)
The User Menu is the top level menu where values for each op-
tion is entered based on the Mode selected. Each option is iden-
tified by a green light when selected. The clock display is the
default home position for the User Menu when OK is selected or
there is no activity for 15 seconds.
Note: Access to all Secondary Menus must originate from
the User Menu. Secondary Menus are identified by the
menu title upon successful entry, e.g. PRO, DIAG and FACT.
The Program Menu is used to edit all program option param-
eters.
The Diagnostic Menu is used to diagnose and troubleshoot
errors with the Intelliswitch™.
The Factory Menu is only to be used when directed to reset or
change factory default settings.
4. User Menu
To enter into the User Menu press the down arrow (menu) or up
arrow. Use the down or up arrow to step through each option.
Each option is identified by a green light when selected.
Options available from the User Menu are:
Mode
Fan Speed
Delay Time
Thermostat degree type
Thermostat Set Point
Start Time
Stop Time
Thermostat Control Mode
Time Set
Day Set
Lock/PASScode
4.1. Mode: single-level
NOFF-ON-AUTO-DELU-PLUS-PRO1-PRO2-PRO3O
Use left or right arrows to select the desired Mode of Operation.
Press "OK to accept selection.
OFF – air door off.
ON – air door will run when start/stop time is satisfied.
Appendix -14