Installer System Test - Honeywell T7300F Installation Instructions Manual

Series 2000 commercial microelectronic conventional or heat pump thermostat
Hide thumbs Also See for T7300F:
Table of Contents

Advertisement

4. Press Run Program.
Run
Program
Set Program
Set Temperature
Run
Occupied
Unoccupied
Occupied
Program
Start Time
Start Time
Day
Temp
Temporary
Set Current
Clear
Occupied
Day/Time
Start Time
Copy
Continous
Unoccupied
System

INSTALLER SYSTEM TEST

Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.
Table 3. Installer System Tests.
Test
Number
System Test Description
10 to 19
Heating equipment can be turned on and
off.
20 to 29
Emergency heat (Q7300C,D,H [heat
pump models only]) equipment can be
turned on and off.
30 to 39
Cooling equipment can be turned on and
off.
40 to 49
Fan equipment can be turned on and off.
60 0 to
Keyboard keys test.
60 19
70 to 79
Thermostat information including date
code, software versions and subbase
identification are displayed.
To start the system test:
CAUTION
Possible Equipment Damage.
Equipment damage can result if compressor is
cycled too quickly.
The minimum off time for compressors is
bypassed during the Installer System Test.
Key to
Press
Heating Equipment System Test
Heat/Cool Settings
T7300F SERIES 2000 COMMERCIAL MICROELECTRONIC CONVENTIONAL
AM
Change
Time/Temp
Unoccupied
Temp
Mon
Heat/Cool
Occupied 1
Settings
System
Fan
Fan
Heat
Table 4. Installer System Test Options.
Test
Number
10
Enter heating equipment system test.
11
Stage-one heat turns on. The system fan is also energized.
12
Stage-two heat turns on. Stage-one heat and system fan remain on.
13
Stage-three heat turns on. Stage-one and stage-two heat with the system fan
are on.
12
Stage-three heat turns off.
11
Stage-two heat turns off.
10
Stage-one heat and system fan turn off.
Press and hold the increase
the same time, until 10 appears. All segments of the LCD
are displayed for three seconds before 10 appears. See
Room
Fig. 5 and 6.
Auto
M4954A
Set Program
Em Ht
Em Ht
Aux Ht
Aux Ht
Comm
Mon
TueWedThuFriSatSun
Un
Occupied 12 Override
System
Em Heat
NOTE: If a duct temperature sensor is installed, the duct
temperature is also displayed.
Refer to Table 4 and Thermostat Information section for
directions and results of the specific system tests.
NOTE: Press Run Program to exit the system test. The
system test times out after four minutes without
any key presses.
7
OR HEAT PUMP THERMOSTAT
and
Start Time
Set Day/Time
Set Day/Time
AM
PM
In
Recovery
Lo
Med
Off
Cool
Auto
Wait
Fig. 5. LCD Display of all segments.
TEST NUMBER
Fig. 6. Test number display.
Description
decrease keys, at
Temporary Setting Enrg
Sav
Room
%Humid
Heat
Cool
Remote
Auto
Only
Duct
Hi
Fan
On
Auto
M4916
M10257A
62-0125—3