10. Overall Verification
10.2 O
C
PTIONAL
ONTROLS
First, turn OFF the main control device Basic,VT1W, VT2W, Platinum or 3-Position Switch before checking the remote optional control(s).
20-
-
:
MINUTE PUSH
BUTTON
(Available only for HRV100H and HRV200H
models.)
Activate the push-button.
Results expected:
1. Motor speed: High for 20 minutes.
2. Indicator light goes "ON".
3. Air exchange indicator light goes "ON"
(VT2W control only).
60-
:
MINUTE CRANK TIMER
Activate the timer.
Results expected:
1.
Motor speed: High for either 20, 40 or 60 minutes.
2.
Air exchange indicator light goes "ON" (VT2W control only).
High speed activation time
20 minutes
40 minutes
60 minutes

11. Maintenance / Instructions for User

Risk of electrical shocks. Before performing any maintenance or servicing, always disconnect the unit from its
power source.
Review with the user the steps required for the regular maintenance of her/his ventilation system. These steps are described in details
in the user manual:
Warn the user of the necessity to rebalance the system following a major house renovation or following the installation of any extra
registers.
Make sure the user understands how to use the main control as described in the user manual.
Do not oil the motor. It is already permanently lubricated.
(cont'd)
VC0030
Position of dial
1 to 19
20 to 39
40 to 60
FOUR TIMES A YEAR:
Inspect the intake hood, and clean if needed.
Clean the filters.
Clean the interior of the cabinet and clean the door.
Clean the condensation tray and inspect the drain tubing (if need be).
ONCE A YEAR:
Clean the recovery core.
Clean the blades of the blower wheels if needed.
20/40/60-
MINUTE PUSH
(Not available for HRV100H and HRV200H
models.)
Activate the push-button. Within 2 seconds,
push one time for 20 minutes, two times for
40 minutes or three times for a 60-minute
ON
activation.
Results expected:
1. Motor speed: High for 20, 40 or 60 minutes.
2. Indicator light goes "ON" and flashes
every 5 seconds (one time to indicate a
20-minute operation, two times for a
40-minute, and three times for a 60-minute operation).
3. Air exchange indicator light goes "ON" (VT2W control only).
NOTE: To stop activation, push one more time.
WARNING
!
CAUTION
26
-
:
BUTTON TIMER
VC0046
TURN
PAST
20
60
VC0017
20 min.
40 min.
60 min.
OFF
10
20
30
40
50