Connecting Duct To The Unit - Broan 1001 ERV Installer Manual

Ventilation system
Hide thumbs Also See for 1001 ERV:
Table of Contents

Advertisement

5. Installation
5.5 C
D
ONNECTING
UCTS TO THE
Insulated flexible duct
Use the following procedure for connecting the insulated flexible duct to the ports on the unit (exhaust to outside and fresh air from outside).
a)
Pull back the insulation to expose the flexible duct.
b)
Connect the interior flexible duct to the port using a duct tie.
c)
Carefully seal the connection with duct tape.
d)
Pull the insulation over the joint and tuck it between the inner and outer rings of the double collar.
e)
Pull the vapor barrier over the insulation and over the outer ring of the double collar.
f)
Apply duct tape to the joint making an airtight seal. Avoid compressing the insulation when you pull the tape tightly around the joint.
Compressed insulation loses its R value and causes water dripping due to condensation on the exterior surface of the duct.
Make sure that the vapor barrier on the insulated ducts does not tear during installation to avoid condensation
within the duct.
a)
VJ0001
Rigid duct:
Use duct tape to connect the rigid ducts to the ports.
Do not use screws to connect rigid ducts to the ports.
Make sure that the 2 balancing dampers are left in a fully open position
before connecting the ducts to these ports (fresh air distribution port
and stale air exhaust port as shown on figure 14).
(cont'd)
U
NIT
b)
c)
VJ0002
CAUTION
CAUTION
d), e)
VJ0003
VJ0004
VJ0009
13
f)
VJ0005
Figure 14