Setting up typical systems FURNACE & HEAT PUMP (DUAL FUEL)
icomfortt−enabled Furnace & icomfortt−enabled HP unit (Dual fuel)
Dual fuel system using an icomfort−enabled gas furnace
(G71MPP, SLP98, SL280) with an icomfort−enabled heat
pump (XP17 or XP21 only).
1. Wiring
see Communicating System Wiring diagram
on Page 34 and Optional Accessories Wiring
(Page 35) for any accessories being installed with the
system.
4−conductor thermostat wire from the icomfort Touch
D
thermostat to the gas furnace (R, i+, i−, C)
4−conductor thermostat wire from the furnace termi-
D
nal strip to the icomfort−enabled HP (R, i+, i−, C)
D
Wiring as required for accessories
2. DO NOT cut any option link on furnace control.
3. After the entire system is wired, power up the system; the
icomfort Toucht thermostat will check the system for
installed communication devices.
4. On the thermostat, go past the add/remove non−commu-
nicating devices" to the adjust a device" screen. Select
the system 49W95 from the device list using the up/down
arrows and press the edit button
5. Select Balance Point Control and press edit. Use the
down arrow to select Enabled" and press save. High and
Low Balance Points will appear in red.
6. Complete Balance Point Control by editing the High and
Low Balance Points. It is not necessary to change the de-
faults, but you must save each setting. The red settings
will go away after pressing save. Press the back button
to return to the adjust screen.
7. Use the arrows to select Furnace" from system devices
list; press edit. From this Furnace screen you will have
access to the various airflow settings. Set the system air
volumes according the needs of the home. When you
change certain settings, the system will prompt you to
please view and save all red settings". Use the arrows
to select the red settings and press edit. Either make
changes or not, but press save either way. The red set-
tings will go away after pressing save. When all CFM set-
tings are complete, press the back button. Press next
step to advance to the tests tab.
8. Test the system operation and confirm the HP unit is elec-
trically energized and operational. Press done.
9. Exit the installer setup mode by selecting the EXIT tab.
TIPS
S
High & Low Balance points are enabled and adjusted un-
der the installer section of the thermostat. In the equip-
ment tab select System 49W95" and press edit. Scroll
down to Balance Point Control" and press edit and se-
lect Enabled and then save.
S
An outdoor temperature sensor is provided in an icom-
fort−enabled heat pump unit. To display the outdoor tem-
perature on the home screen of the thermostat, you must
turn on (or off) the Outdoor Temp Display". From the
Home screen, press press for more area and select the
HELP tab. Press the user preferences box and scroll
down to Outdoor Temp Display". Press the modify but-
ton and use the up/down arrows to select On (or Off) and
then press the save button. Press done to return to the
Home screen.
S
Turn the Indoor Humidity Display on and off in a similar
manner as above.
S
Gas heat is not provided to temper the air during defrost
cycles.
icomfortt−enabled Furnace &
non−communicating HP unit (Dual fuel)
NOTE − DO NOT use a conventional non−communicating
heat pump unit in an icomfort dual fuel system.
TIPS
S
A conventional thermostat capable of controlling a dual
fuel system, like the ComfortSense
lected for this type of application.
Page 39