Installation - Toshiba MMF-AP0154H-E Installation Manual

Multi type floor standing type
Hide thumbs Also See for MMF-AP0154H-E:
Table of Contents

Advertisement

SMMS Floor Standing Type
Installation space
Reserve sufficient space required for installation or service work.
Front side
(In case of right direction piping)
REQUIREMENT
When using the air conditioner under condition of high humidity, attach the heat insulator to the side face and the rear
side of the indoor unit.
Filter cleaning sign term setting
The lighting term setup of the filter sign (Notification of filter cleaning) of the remote controller can be changed
according to the condition of installation.
For setup method, refer to "Filter sign setting" in the Applicable controls of this Manual.
11-EN
Installation Manual
500 or more
200 or
more
Front side
SMMS Floor Standing Type
4

Installation

(Unit: mm)
CAUTION
Strictly comply with the following rules to prevent damage of
the indoor units and human injury.
• Do not put a heavy article on the indoor unit or let a
person get on it. (Even units are packaged)
• Carry in the indoor unit as it is packaged if possible. If
carrying in the indoor unit unpacked by necessity, use
buffering cloth or other material to not damage the
unit.
• Carry the package by two or more persons, and do not
bundle it with plastic band at positions other than
specified.
• Be sure to take measures to prevent falling at the wall
surface and the floor and fix it surely considering
prevention of accident of falling because this unit is
formed into a thin type. If it is not fixed, a falling
accident may occur.
• After carry in the indoor unit to the specified place, fix
it to the wall and the floor immediately for safety.
Installation of indoor unit
Fixing to the wall surface
Use the attached wall fixing bracket by inverting it at
upper side of the unit. Fix the indoor unit to the wall
surface using the attached screw bolts, anchor bolts or
etc. at two positions. A many holes for fixing the indoor
unit to wall surface and for fixing the indoor unit itself
are provided on the bracket. Sliding the bracket right
and left sides, select a position which can securely fix
the indoor unit and then fix it.
Wooden wall
Screw bolts
– 6 –
A hole on the wall fixing bracket for the indoor unit is a
long hole. Therefore the indoor unit can be fixed at any
position keeping clearance from 0 to 50 mm.
As shown below, it is also possible to fix the indoor unit
without inverting the bracket. (In this case, keep
clearance with length of head of the bolt between the
indoor unit and the wall.)
0 mm
50 mm
Fixing to the floor
Use the attached the attached floor fixing bracket to fix
the lower right and left sides of the indoor unit to the
floor.
To fix to the indoor unit, use the side plate screws and
use the screw bolts or anchor bolts for fixing to the floor
respectively, and then fix the indoor unit at total four
positions, two positions for right and left each.
Wooden wall
Screws bolts
(Total 4 at right and left)
Screws for
side plate
Concrete wall
Anchor bolts
Model MMF-
AP015H to AP027H type
AP036H to AP056H type
Installation Manual
Clearance
(Height of head
of fixing bolt)
Concrete wall
Anchor bolts
Screws for
(Total 4 at
side plate
right and left)
B
A
(Unit: mm)
A
B
88
42 to 92
258
52 to 102
EN
12-EN

Advertisement